Marstair DCU+ 15 Скачать руководство пользователя страница 7

 

54208003-13 

 

3. 

Connecting the pipework: 

 

a.  Remove the flare nuts from the suction service valve and the expansion device as appropriate. 
b.  Ensure that both the suction and expansion lines are fully insulated. 
c.  Place the flare nuts over the incoming pipework and flare the pipe ends. 
d.  Connect the pipework between the units. Do not leave pipes ends, valves etc open to the 

atmosphere. Always use 2 spanners when tightening the flare nuts to avoid twisting the pipes. 
Use a small amount of refrigerant oil on the mating surfaces. 

e.  Sight glasses and filters driers are not necessary, but if required should be fitted between the out 

door unit liquid shut off valve and the expansion device on the units. 

 

 

 

EVACUATING

 

1. 

Evacuate  the  interconnecting  pipework  and  indoor  unit  by  connecting  a  vacuum  pump  to  the 
service  ports on the outdoor unit valves and evacuate to 1000 microns (1 Torr) or better: hold for 
a minimum  of 15 minutes. 

2. 

Open the valves slowly using a 5mm Allen key. If no additional charge is required, read note 4. 

3. 

If additional charge is required: 

 

a. 

Start the unit on maximum indoor fan setting (with heat pump systems in AIR 
CONDITIONING  MODE) and allow  the compressor to run for approximately 10 seconds. 

b. 

Allow system pressures to stabilize. 

c. 

Any additional charge should be introduced through the Schrader valve on the indoor 
unit or  the service port  on the suction service valve on the outdoor unit. 

 

Where possible, charge to a sweat line on the evaporator. Typical suction pressures on short lines 
at 

UK  conditions,  with  maximum  evaporator  and  condenser  fan  speeds,  i.e.  during 

commissioning, will  be 55-60 psig. 

 

Take care not to overcharge  the system, otherwise liquid could return to the compressor, 
causing  damage. 

 

 

IF NO ADDITIONAL REFRIGERANT CHARGE IS REQUIRED:

 

Open the valves very slowly using a 5 or 8mm Allen key. On DCU+/DHPU (L) units, remove 

link JP6 

on 

the pcba (identified by a white label), otherwise the fan will always run at maximum speed and the infrared 
handset will be inoperative. Replace the caps on the service ports, (torque to 25NM). 

 

IF ADDITIONAL REFRIGERANT IS REQUIRED:

 

 

1. 

After evacuating the indoor unit and interconnecting pipework, slowly open the valves using 5 or 8mm 
Allen key. The high and low pressure should equalise within a minute. 

 

2. 

Additional charge should be introduced with the system running in the 

air conditioning mode 

(including 

heat pumps). See indoor unit instruction for additional system charge. 

 

3. 

DCU+/DHPUL units are all

 

fitted with head pressure control. The link wire across the orange terminals 

(DCU+) and link between terminal 1 & 6 (DHPUL), allows the fan to operate at full speed. 

THIS 

SHOULD BE REMOVED AFTER CHARGING

 

 
 
 

ADDITIONAL REFRIGERANT - pipe runs over 7.5m.

 

 

Add refrigerant and oil for each additional meter over 7.5m, based on the following: 

 

 

 

 
 
 

Expansion line size.

 

3/8" 

1/2" 

5/8" 

Additional refrigerant (g/m).

 

16 

30 

48 

Additional POE oil

 

25g per 350g of additional 

refrigerant to a maximum of 300g 

 

Additional polyolester oil: 
L’Unite 181-023, 
ICI Emkarate RL32S or 
RL32CF,  Mobil Arctic 
EAL22 or EAL22C. 

REFRIGERANT 

 

Содержание DCU+ 15

Страница 1: ...g parts and refrigerant under pressure Always site out of reach of children and protect from vandalism 3 The units have fan speed control start delay timer HP and LP switches and a contactor fitted as...

Страница 2: ...560 1174 490 65 65 240 392 865 404 81 DCU 60 1100 510 560 1174 490 65 65 240 392 865 404 81 DCU 80 1100 510 560 1174 490 65 65 240 392 865 404 84 DHPU L 15 930 510 495 1004 490 65 120 210 317 757 354...

Страница 3: ...ers to suit IMPORTANT The stabilizing brackets provided MUST be used when suspending a unit Fit the stabilizing brackets to the top corners of the backpanel and front face using the No 10 screws provi...

Страница 4: ...n thickness of at least 45mm is recommended 1 To maximise performance pipe runs should be kept as short as possible However individual pipe runs to a maximum of 80m 50m on sizes 15 20 including 20m li...

Страница 5: ...Use the shortest possible route avoiding sharp bends 5 Fully insulate both the suction and expansion lines including the expansion device since both lines may sweat FITTING LOSSES in equivalent strai...

Страница 6: ...check valve is needed The expansion assembly and line must be fully insulated Note The indoor units listed below are fitted with heating capillarys WM60H WM80H WM100H CC875 80H CC875 110H CC875 140H H...

Страница 7: ...le charge to a sweat line on the evaporator Typical suction pressures on short lines at UK conditions with maximum evaporator and condenser fan speeds i e during commissioning will be 55 60 psig Take...

Страница 8: ...t to suit the refrigerant It may be necessary to adjust this to suit site conditions to raise or lower the nominal head pressure a With the system switched off connect a high pressure gauge to the liq...

Страница 9: ...hanges per turn of adjusting screw Pressure change 1 4 0 12 5 bar Clockwise 1 2 bar counter clockwise 1 2 bar Pressure change 2 9 2 21 2 bar Clockwise 2 5 bar counter clockwise 2 5 bar Pressure change...

Страница 10: ...hed cables ElectromechanicalSystems Systems including an electromechanical indoor unit require a supply to the condensing unit with connecting cables run to the indoor unit Electronic Systems It is re...

Страница 11: ...400V 3 50Hz disjoncteur a fournir 400 3 N 50 abgesicherts versorgung 400V 3 50Hz S S 1 3 7 S S Signal Ansteurung 230V 50Hz 1 3 7 S S SIGNAL 1 230V 50Hz 7 POWER TO SUIT SUPPLY FUSE PUISSANCE FOURNIR U...

Страница 12: ...characteristics that allow starting of the compressor yet still afford close overcurrent protection under running conditions The ratings shown are for HRC motor rated fuses DUCTED UNITS DCU 15 DCU 20...

Отзывы: