-7-
Electrical Loads (At 230 Volts 50 Hz 1Ph or 400 Volts 50 Hz 3PhN)
HL/HLR
380
460
540
FAN MOTOR
1.3
1.4
1.6
MCU(+)
90
100
130
165
FAN MOTOR
1.0
1.0
1.2
1.2
R407C COMPRESSOR (1 PHASE) NOMINAL FLA
15.9
--
--
--
R407C COMPRESSOR (3 PHASE) NOMINAL FLA
6.1
6.2
6.7
8.5
R22 COMPRESSOR (1 PHASE) NOMINAL FLA
15.2
--
--
--
R22 COMPRESSOR (3 PHASE) NOMINAL FLA
6.0
6.1
6.4
8.3
MHPUE
90
100
130
FAN MOTOR
1.0
1.2
1.2
R407C COMPRESSOR (1 PHASE) NOMINAL FLA
15.9
--
--
R407C COMPRESSOR (3 PHASE) NOMINAL FLA
6.1
6.2
6.7
R22 COMPRESSOR (1 PHASE) NOMINAL FLA
15.2
--
--
R22 COMPRESSOR (3 PHASE) NOMINAL FLA
6.0
6.1
6.4
Recommended Fuse Sizes (R22 and R407C systems)
The system and its supply/interconnecting wiring must be protected by fuses, preferably High Rupture Current (HRC)
motor rated types (to EN 60269) or miniature circuit breakers (to EN 60898) or local codes having similar time lag
characteristics, that allow starting of the compressor yet still afford close overcurrent protection under running
conditions. The ratings below are for HRC motor rated fuses.
Air Conditioners
HL/HLR + MCU(+)
380 + 90
380 + 100
460 + 100
460 + 130
540 + 130
540 + 165
1 Phase cool only
32
--
--
--
--
--
3 Phase cool only
16
16
16
16
16
20
Heat Pumps
HL/HLR + MHPUE
380 + 90
460 + 100
540 + 130
1 Phase cool only
32
--
--
3 Phase cool only
16
16
20
Содержание 526 HL Series
Страница 13: ... 13 ...
Страница 16: ... 16 HL WIRING DIAGRAM HLR WIRING DIAGRAM ...
Страница 17: ... 17 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Страница 18: ... 18 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Страница 19: ... 19 MHPUE WIRING DIAGRAMS 1 Phase MHPUE 90 3 Phase MHPUE 90 ...
Страница 20: ... 20 3 Phase MHPUE 100 to 130 ...
Страница 21: ... 21 HL INTERCONNECTING WIRING DIAGRAMS HL 380 1 Phase MCU 90 HL 380 to 460 3 Phase MCU 90 to 100 ...