
-31-
FAULT FINDING
CONDITION
POSSIBLE CAUSE
ACTION
A
Indoor fan motor will not run
No electric supply at socket or switched fuse
box
Check fuse rating and replace if necessary.
Check for loose electrical connections
Unit wiring fault
Check wiring and connections
Fan motor capacitor defective
Replace if faulty
Fan motor defective
Replace if faulty
Internal fuse blown
Clear fault and replace fuse
B
Inadequate cooling or heating
Dirty evaporator fins/filter
Clean if blocked
Evaporator motor not running
As in section A
Refrigerant shortage or excess
Check for leaks. Repair, evacuate and
recharge or check for high head pressure and
recover refrigerant if necessary
Faulty thermostat or incorrectly set
Replace if faulty
Dirty condenser
Clean if necessary
Faulty compressor
Replace
LP cutout circuit open (if fitted)
Check as refrigerant shortage or excess
C
Compressor and outdoor fan motor
will not run
LP cutout circuit open (if fitted)
Check as above
No electric supply at socket or switch fuse box
Check fuse rating and replace if necessary.
Check for loose electrical connection.
Unit wiring fault
Check wiring and connections
Capacitor, thermostat, relay or overload
defective
Replace if faulty
Compressor failure
Replace if faulty
Controls not set properly
Check and rectify
Off cycle delay operating
If applicable, wait 3 minutes
High condensate level detected
See G
D
System runs for long periods and
will not cycle
Unit underrated for conditioned area
Check heat load against capacity
Thermostat not operating correctly
Check wiring, position of phial and operation
Refrigerant shortage
Check for leaks. Recover, repair, evacuate
and recharge
Indoor coil dry or partly sweating
Dirty condenser
Clean fins if necessary
E
Indoor coil frosting
Refrigerant shortage
Check for leaks. Recover, repair, evacuate
and recharge
Dirty evaporator fins/filter
Clean if blocked
Running in cool ambient without a head
pressure controller
Fit head pressure controller
If room temperature is also low
Thermostat set too low or cooling permanentlyReset or replace
F
Noisy unit
Fan fouling cowl (outdoor unit)
Realign fan
Worn motor bearing
Replace motor
Casing or piping vibration
Check cause and rectify
Loose parts or mounting
Find and tighten
Bent fan blade
Replace fan
G
Water leaking from unit
Blocked drain
Clear obstruction
Units with condensate pump
No supply to pump or loose connection
Secure the supply
Fouled sensor
Clean sensor
Pumping slowly
Check drain pipes; if clear, replace pump
Pump windings shorted
Replace pump
H
Pump always runs
Faulty sensor or pcb
Replace sensor or pcb
I
No heating (Heat pump systems
only)
Controls not set for heating
Reset
Unit wiring fault
Check wiring and connections
Dirty evaporator fins/filter
Clean
Faulty thermostat
Check for signal; replace if faulty
Reversing valve jammed
A light tap may free it; preferably replace
J
Overload tripped on three phase
units
High voltage supply
Max rated voltage 254v -- check supply
Compressor failure
Replace
Fuses blown
Replace fuses and investigate reason for
fuses blowing
Содержание 526 HL Series
Страница 13: ... 13 ...
Страница 16: ... 16 HL WIRING DIAGRAM HLR WIRING DIAGRAM ...
Страница 17: ... 17 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Страница 18: ... 18 MCU WIRING DIAGRAMS 1 Phase MCU 90 3 Phase MCU 90 to 100 3 Phase MCU 130 to 165 ...
Страница 19: ... 19 MHPUE WIRING DIAGRAMS 1 Phase MHPUE 90 3 Phase MHPUE 90 ...
Страница 20: ... 20 3 Phase MHPUE 100 to 130 ...
Страница 21: ... 21 HL INTERCONNECTING WIRING DIAGRAMS HL 380 1 Phase MCU 90 HL 380 to 460 3 Phase MCU 90 to 100 ...