Marra Forni
10310 Southard Drive Beltsville, MD 20705 1.888.239.0575 [email protected]
STRUCTURAL BUILD OF OVEN / VENTING
A UL-listed grease or building heating appliance chimney installation (referred to as direct venting),
and Type I exhaust hood installed per NFPA 96 and UMC standards for Ventilation Control and Fire
Protection of Commercial Cooking Operations are the only two methods of venting permitted for
commercial Marra ovens. Of the two options, direct venting is more common, although an exhaust
hood is required in some areas (consult local ordinances). Venting must comply with ETL regulations.
For gas ovens, always ensure that there are no obstructions to the flow of combustion and ventilation,
including the cylinder enclosures. Please refer to your exhaust hood manufacturer’s guidelines for
inspection, maintenance and sanitation procedures.
A UL Listed Grease Duct/Building Chimney Heating Appliance
can be connected to the
chimney opening of the oven. A minimum 50v0 C.F.M.-listed power ventilator for restaurant exhaust
appliances is required. A minimum temperature rating of 300°F is required for the power ventilator.
Type I Exhaust hood standards for ventilation control and fire protection of commercial
cooking operations are as follows:
Steel baffle (NOT MESH) grease filters must be used and
placed at the rear of the hood. The following specifications must also be met:
• There must be at least 10” between the front of the oven face and the front of the hood.
• According to UMC there must be 42” between the oven heart and the face of the filter.
• The side of the hood must extend a minimum of 6” to either side of the oven door opening.
• If required, a type 1 hood must be placed above the cooking opening and set atop the oven.
Minimum hood dimensions are 36” wide and 37” deep, 22” high for Models 90 and 110, and 40” wide,
37” deep and 22” high for 140 and 150.
Duct Velocity = 1500-2500 FPM - Vol.: 800-1000 CFM
Refer to Lennox Chimney Supply instructions for specific Direct Venting installation requirements. A
field-built duct, constructed and installed to NFPA 96 or International Mechanical Code grease duct
specifications, may also be used.
Volume: 150-200 CFM
www.SecurityChimneys.com
From Inside to Outside:
- 8 cm thick bricks layered, wrapped in mesh
- 3 cm refractory mortar sprayed over mesh
- 4 cm Fyrewrap insulation
- 6 cm Thermafiber mineral wool insulation
- 3 cm refractory mortar
- 6 cm refractory brick
- 1 cm refractory mortar
- 6 cm refractory brick
- 3 cm Thermafiber mineral wool
- 4 cm Fyrewrap insulation
- 2 mm metal