background image

Note to Installer: Converting heater to half wattage
(Not applicable to WH3150 and WH3180, 120 Volt Models)

The WH Series wall heaters are manufactured and shipped at the higher
rated wattage.  Full wattage heaters can be converted to half wattage by
doing the following steps.
1.

Remove the red jumper wire as shown in Figure 3 and discard.

2.

To permanently make the heater half wattage, cut the male terminal
spade, carefully not to damage the cold pin and discard.

3.

Mark the wattage of the heater on the white label inside the backbox.

Installation of Back Box with Optional 

Surface-Mounting Frame WHSM (See Figure 4)

1. Secure back box to wall with knockouts in upper right hand corner using

screws and anchors.

2. Hang the surface-mounting frame on the back box. Ensure that the back

edge of the surface-mounting frame is flush against the wall.

NOTE:

If heater is located in a high traffic area, where it may be subject-

ed to vandalism or abuse, take extreme care to see that the box is firmly
attached to the wall.

3. Power Supply Wiring

NOTE:

Wiring Compartment Volume - 119in

3

(1950cm

3

).

a. Run a power supply cable into the area to the right of the mounting

frame. Arrangement of wiring to this point must be in accordance
with National and Local codes.Refer to specifications on page 2 for
proper wire size.

NOTE:

If the wiring is to run through the wall, cut a hole in the area of the top

of the back box. Run the supply wire through this hole. Then remove the
“knockout” from the top of the box and 
proceed to step C.

b. Remove the “knockout” on the top side of the frame.

c. Remove disconnect switch bracket by loosening the two screws on

the right side.

d. Feed the power supply cable through the frame allowing 6" (152mm)

of lead to remain inside the back box (using cable clamp, connector,
or other suitable strain relief).

e. Secure the power supply cable to the back box (using cable clamp,

connector, or other suitable strain relief) allowing 6" (152mm) of lead
to remain inside the back box.

f. Connect supply wires to blue wires of disconnect switch using wiring

connectors (see wiring diagram, pg. 4).

g. Ground the back box by connecting the supply ground leadwire to

the green ground screw located in the inside top of the back box.

h. Secure disconnect switch bracket in place.

Installation of Heater Assembly and Grille

After back box is completely installed and no further construction dirt is expect-
ed, clean debris from back box and remove heater assembly from its carton.
Then refer to Figure 5 and proceed as follows:

1.  Insert the heater assembly into back box, placing the four mounting holes

(with key-hole slots) over the screws in the box. Tighten all screws securely.

2. If surface-mounting frame is used, ensure that the frame is even with all four

heater assembly tabs before tightening screws.

3. Connect the two disconnected switch wires to the heat control switch (ther-

mostat) leads using wirenuts. After connection, push wires back into the
opening.

4. Turn thermostat to the extreme counterclockwise position.
5. Push disconnect switch into ON position.
6. Latch at bottom of heater assembly should be in up position.
7. Mount grille over tabs on fan deck and push down until grille is secure.
8. Insert screwdriver through bottom louver in grille and loosen screw while

holding bottom of grille against wall. This will allow latch to drop in place.
Tighten screw.

Operation

1.

Rotate the thermostat fully clockwise. This should energize the heating
elements and cause warm air to flow from the hot air discharge at the
openings in the bottom of the grille.

2.

After the operation check, rotate the thermostat to the desired position to
obtain room comfort.

NOTE: 

For best results, the heater should be left “ON” 

constantly during the heating season because the thermostat, when properly
set, will maintain the desired temperature.

Cleaning & Maintenance

To maintain optimum performance and efficiency, heater should be cleaned
and checked periodically. It is recommended the heater be cleaned at least
annually. (more often if used in a dirty environment)

TO CLEAN HEATER:

1. Disconnect power to heater at main panel or breaker.
2. Remove thermostat knob (if provided) and remove front cover (grille)

as follows: (See figure 4)

–Insert screw driver through bottom louver and loosen one screw that

holds latch mechanism.

–Lift front cover upward and pull top outward to remove.

3. Push ON/OFF switch to OFF position.
4. Using vacuum cleaner knozzle, brush, or dust cloth, remove dust and

any foreign material from heater. Use care to not bend fan blade or
damage heater wiring. (Spin blade by hand to make sure it turns freely.)

5. Push ON/OFF switch to ON position.
6. Replace front cover and secure latch mechanism. (See installation of

Heater Assembly and Grille.)

7. Reconnect power to heater and verify that heater operates  properly.

Male terminal spade

Red jumper wire 

Fig. 4: Surface Mounting 
Installation

MOUNT BACK BOX

TO WALL USING

REAR MOUNTING

HOLES.

HANG FRAME

ON BACK BOX.

15-5/32 "
(385mm)

19" 

(482mm)

3-13/16"

(97mm)

Fig. 5

Fig. 3

3

CAUTION

TO PREVENT POSSIBLE ELECTRIC SHOCK, ALWAYS DISCON-
NECT ALL POWER TO HEATER AT MAIN DISCONNECT PANEL
OR FUSE BOX BEFORE CLEANING OR MAINTENANCE TO
HEATER.

!

!

Содержание WH Series

Страница 1: ...ll wiring must be in accordance with the National and Local Electrical Codes and the heater must be grounded 3 Verify the power supply voltage coming to heater matches the ratings printed on the heater nameplate before energizing 4 This heater is hot when in use To avoid burns do not let bare skin touch hot surfaces 5 Do not insert or allow foreign objects to enter any ventilation or exhaust openi...

Страница 2: ...ides of box Top flange of back box should protrude approximately 1 2 or 12 7mm from finished wall surface b Secure the back box in place with wood screws or nails 4 Wiring Disconnect Switch a Connect the power supply wires to the blue wires of the disconnect switch using wire connectors see wiring diagram pg 4 b Ground the back box using the green ground screw located in the inside top of the back...

Страница 3: ...to Figure 5 and proceed as follows 1 Insert the heater assembly into back box placing the four mounting holes with key hole slots over the screws in the box Tighten all screws securely 2 If surface mounting frame is used ensure that the frame is even with all four heater assembly tabs before tightening screws 3 Connect the two disconnected switch wires to the heat control switch ther mostat leads ...

Страница 4: ...WIRING DIAGRAM FOR 4800 WATT 208 VOLT SINGLE PHASE WALL HEATER Wiring Diagrams WIRING DIAGRAM FOR THREE PHASE WALL HEATERS 1500 1800 4800 4000 3000 WATT HEATERS 120V 208V 240V OR 277V See diagram no 2 for 4800W 208V 1Ph Full wattage heaters can be converted to half wattage by moving the red jumper wire connecting the top and bottom element terminals NOTE Conversion not applicable to 120V models 20...

Страница 5: ... inoperative units should be returned to the nearest Marley authorized ser vice center or the Marley Engineered Products Center and we will repair or replace at our option at no charge to you with return freight paid by Marley It is agreed that such repair or replacement is the exclusive remedy available from Marley Engineered Products THE ABOVE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES EXPRE...

Отзывы: