troubleshooting

Trouble

Cause

Remedy

Motor does not come up to 

speed

Voltage too low at motor 

terminals because of line drop

Check transformer and setting of taps. Use higher voltage on 

transformer terminals or reduce loads. Increase wire size or reduce 

inertia.

Broken rotor bars

Look for cracks near the rings. A new rotor may be required. Have 

motor service person check motor.

Wrong motor rotation

Wrong sequence of phases

Switch any two of the three motor leads.

Geareducer noise

Geareducer bearings

If new, see if noise disappears after one week of operation. Drain, flush 

and refill Geareducer oil. See Geareducer User Manual. If still noisy, 

replace.

Gears

Correct tooth engagement. Replace badly worn gears. Replace gears 

with broken or damaged teeth

Unusual fan drive vibration

Loose bolts and cap screws

Tighten all bolts and cap screws on all mechanical equipment and 

supports.

Unbalanced driveshaft or worn 

couplings

Make sure motor and Geareducer shafts are in proper alignment and 

“match marks” properly matched. Repair or replace worn couplings. 

Rebalance driveshaft by adding of removing weights from balancing 

cap screws. See Driveshaft User Manual.

Fan

Make certain all blades are as far from center of fan as safety devices 

permit. All blades must be pitched the same. See Fan User Manual. 

Clean off deposit build-up on blades

Worn Geareducer bearings

Check fan and pinion shaft endplay. Replace bearings as necessary.

Unbalanced motor

Disconnect load and operate motor. If motor still vibrates, rebalance 

motor.

Bent Geareducer shaft

Check fan and pinion shaft with dial indicator. Replace if necessary.

Fan noise

Blade rubbing inside of fan 

cylinder

Adjust cylinder to provide blade tip clearance.

Loose bolts in blade clamps

Check and tighten if necessary

Scale or foreign substance in 

circulating water system

Insufficient blowdown

See “Water Treatment” section of this manual.

Water treatment deficiency

Consult competent water treating specialist. See “Water Treatment” 

section of this manual.

Cold-water temperature too 

warm 

(see “Tower Operation”)

Entering wet-bulb temperature 

is above design

Check to see if local heat sources are affecting tower. See if 

surrounding structures are causing recirculation of tower discharge air. 

Discuss remedy with Marley representative.

Design wet-bulb temperature 

was too low

May have to increase tower size. Discuss remedy with Marley 

representative.

Actual process load greater 

than design

May have to increase tower size. Discuss remedy with Marley 

representative.

Overpumping

Reduce water flow over tower to design conditions.

Tower starved for air

Check motor current and voltage to be sure of correct contract power. 

Repitch fan blades if necessary. Clean louvers, fill and eliminators. 

Check to see if nearby structure or enclosing walls are obstructing 

normal airflow to tower. Discuss remedy with Marley representative.

Excessive drift exiting tower

Distribution basins overflowing

Reduce water flow rate over tower to design conditions. Be sure hot 

water basin nozzles are in place and not plugged.

Faulty drift elimination

Check to see that integral fill, louvers and eliminators are clean, free 

of debris and installed correctly. If drift eliminators are separate from 

fill, make sure they are correctly installed in place. Clear if necessary. 

Replace damaged or worn out components.

Содержание Quadraflow

Страница 1: ...Quadraflow cooling tower INSTALLATION OPERATION MAINTENANCE sea_Z0238885_D ISSUED 8 2018 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual ...

Страница 2: ...ions 18 Motor Relubrication Instructions 19 Prolonged Shutdown 19 Additional Services 20 Additional Information 21 Troubleshooting 22 The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product Note Indicates presence of a hazard which can cause severe personal injury...

Страница 3: ...uestions about the operation and or maintenance of this cool ing tower and you don t find the answers in this manual please contact your Marley sales representative When writing for information or when ordering parts pleaseincludetheserialnumbershownonthecoolingtowernameplate Tower Location Space available around the tower should be as generous as possible to pro mote ease of maintenance and to pe...

Страница 4: ...tor Our subcon tractors provide safe efficient assembly which complies with all requirements for five year warranty protection of your tower by SPX Motor Wiring Wire motor leads as shown on the motor nameplate matching the supply voltage Do not deviate from the motor nameplate wiring Internal space heaters may be present depending upon the motor manufac turer For space heater operation and wiring ...

Страница 5: ...limit amp draw to nameplate amps during cold weather opera tion If furnished with a mechanical O L set this at 110 over motor nameplate amps Motor rotation must be the same in both VFD mode and By pass mode If cable distance between the VFD and motor is greater than 30 me ters a DV DT output filter is recommended to avoid damage to the motor 30 meters distance is based on our field experience the ...

Страница 6: ...e responsibility for any technical support or damages for problems associate with non Marley brand VFD systems Changing the operational fan speed from the factory settings could cause the fan to operate in an unstable region which may result in damage to the equipment and possible injury Mechanical Equipment Always make certain that mechanical equipment is inoperable during periods of maintenance ...

Страница 7: ...heat load General The cold water temperature obtained from an operating cooling tower will vary with the following influences 1 Heat Load With the fan in full operation if the heat load increases the cold water temperature will rise If the heat load reduces the cold water temperature will reduce Note that the number of degrees range through which the tower cools the water is established by the sys...

Страница 8: ...the motor can be restarted Fan cycling limits Considering the normal fan and motor sizes utilized on Quadraflow towers anticipate that approximately 4 to 5 starts per hour are al lowable If your tower is equipped with a two speed motor greater opportunity for temperature control is afforded you When the water temperature becomes too cold switching the fan to half speed will cause the cold water te...

Страница 9: ... entire hot water basin and hot water inlet Make sure that cold water suction screens are clear and installed in place 4 Fill the water system to an approximate depth of 76mm in the elevated section of the cold water basin This is the recommended operating water level Adjust the float valve so that it is essentially closed at that level Continue filling the system until the water reaches a level a...

Страница 10: ...ithout circulating stagnant water over the cooling tower fill or operating the cooling tower fan After biocidal pretreatment has been successfully completed cooling water may be circulated over the tower fill with the fan off When biocidal treatment has been maintained at a satisfactory level for at least six hours the fan may be turned on and the system returned to service Resume the standard wat...

Страница 11: ...page 8 However in towers of more than one cell where fans are manipulated sequentially please realize that the water temperature will be significantly lower in the cell or cells operating at the highest fan speed than the net cold water temperature produced by the entire tower would indicate Wintertime operation of multicell towers at low cold water temperature levels requires that the operator be...

Страница 12: ...ontrol during freezing weather Towers must not be operated with reduced water rate and or no heat load during freezing weather If the circulating water system cannot be shut down water returning from the process should be made to bypass the tower If a bypass is used all water must be bypassed without modulation If the water bypass is directly into the tower s cold water basin its design must be ap...

Страница 13: ...oevaporate Although the water lost by evaporation is replenished by the makeup system it exits the tower as pure water leaving behind its burden of dissolved solids to concentrate in the remaining water Given no means of control this increasing concentration of contaminants can reach a very high level In order to achieve water quality which is acceptable to the cooling tower as well as the remaind...

Страница 14: ...e water treatment professional to clean and treat your cooling tower See Tower Startup section of this manual Cooling towers must be cleaned and disinfected regularly in accordance with ASHRAE Standard 188 and Guideline 12 Workers performing decontamination procedures must wear personal protective equipment PPE as directed by their facility safety officer Cooling towers must be visually inspected ...

Страница 15: ...urning the power back on Service personnel must wear proper personal protective clothing and equipment Weekly Visually inspect the cooling tower to assess general operating conditions and for signs of microbial growth and appearance of debris scale and corrosion Refer to ASHRAE Standard 188 and Guideline 12 for specific frequency recommendations Consult a knowledgeable water treatment professional...

Страница 16: ...gion including the fan guard Use torque settings prescribed on the fan nameplate To maintain five year change intervals use only oil designed specifi callyfortheseGeareducers If afterfiveyears turbine typemineraloil is used the oil must be changed semiannually Refer to Geareducer User Manual for oil recommendations and further instructions Annually Inspect the tower thoroughly making maximum use o...

Страница 17: ...x Check for loose driveshaft or coupling fasteners x Check driveshaft flex element for unusual wear x x Lube lines Check for oil leaks in hoses or fittings x x Fan Check and tighten blade and hub fasteners x Check fan blade pitch and tip clearance x Check fan cylinder for loose fasteners x Motor Lubricate as required R Check mounting bolts for tightness x Operate at least 3 hours a month 3 hours a...

Страница 18: ...ft service manual Fan Check fan assembly bolting and tighten as required Use torque settings prescribed on the fan nameplate Refer to fan service manual Fan Motor Clean and lubricate motor if required at close of each operating season refer to motor manufacturer s recommendations Does not apply to motorswithsealedbearings Checkmotoranchorboltsandtightenasrequired Do not start motor before determin...

Страница 19: ...t apply to motors with sealed bearings FiberglassComponents Checkallfiberglasspartsforexposedglassfibers If found the affected surfaces should be roughened up and solvent wiped Surfaces must be clean and dry and free of oil grease or other contaminants before applying new coating The best coating system requires using a two part polyamide epoxy primer to promote adhesion and a two part acrylic pol...

Страница 20: ...and operating characteristics intended A complete stock of all parts and components is maintained at one or more of the various Marley plants In cases of emergency they can normally be shipped within 24 hours by air freight if necessary However you would obviously benefit from anticipating your need in advance thus avoiding the cost of special handling Be sure to mention your tower serial number f...

Страница 21: ...assembly and instal lation These drawings and manuals contain important information relating to safe installation and operation of the cooling tower A separate installation drawing for each purchased option is included in the document package If you have purchased an option and can t find the ap propriate installation drawing contact your local Marley sales representative before proceeding SPX als...

Страница 22: ...cket fits or bearing Rotor unbalance Rebalance Cooling fan hitting end bell guard Reinstall or replace fan Motor runs hot Wrong voltage or unbalanced voltage Check voltage and current of all three lines against nameplate values Overload Check fan blade pitch See Fan User Manual Check for drag in fan drivetrain as from damaged bearings Wrong motor RPM Check nameplate against power supply Check RPM ...

Страница 23: ... shaft with dial indicator Replace if necessary Fan noise Blade rubbing inside of fan cylinder Adjust cylinder to provide blade tip clearance Loose bolts in blade clamps Check and tighten if necessary Scale or foreign substance in circulating water system Insufficient blowdown See Water Treatment section of this manual Water treatment deficiency Consult competent water treating specialist See Wate...

Страница 24: ...nological progress all products are subject to design and or material change without notice SPX COOLING TECHNOLOGIES MALAYS IA Sdn Bhd UNIT 505 BLOCK B PHILEO DAMANSARA 2 NO 15 JALAN 16 11 OFF JALAN DAMANSARA 46350 PETALING JAYA MALAYSIA 60 3 7947 7800 th my enquiry spx com spxcooling com Quadraflow USER MANUAL ...

Отзывы: