Marley Geareducer 32.2 Скачать руководство пользователя страница 7

 7

repair and lubricants

Table 1  Oil viscosity

Repair and Overhaul

If your Geareducer ever needs replacement or repair, SPX Cooling 
Technologies recommends returning the unit to a Marley factory 
service center. Contact your Marley sales representative to discuss 
a course of action. The Marley Order Number on your cooling 
tower will be required if the Geareducer is shipped back to the 
factory for repair. Obtain a 

“Customer Return Material”

 tag from 

the Marley sales representative in you area. To find your Marley 
sales representative call 

913 664 7400

 or check the internet at

 

spxcooling.com

.

Major repairs require the use of a fully equipped machine shop. 
If you decide to repair or overhaul your Geareducer, refer to the 

Field Repair

 Section and Geareducer 

Parts List

.

Suggested Lubricants

The following list of lubricants in 

Table 1

 is provided as reference 

only. These products have been recommended by their respective 
manufacturers as acceptable for use in a Marley spiral bevel and/
or helical Geareducer for cooling tower applications. This list is 
not an attempt to include all the lubricants that may be satisfac-
tory. If lubricants other than those listed are used they must not 
contain any additives—such as detergents or EP additives—which 
are adversely affected by moisture and could reduce the service 
life of the Geareducer. Suitability of lubricants used other than 
those listed rests with the customer/owner and lubricant supplier.

Winter or Summer

Severe Duty/High Temperature

Air Temperature at Geareducer

Below 110°F (43°C)

Above 110°F (43°C)

ISO 150

ISO 220

Содержание Geareducer 32.2

Страница 1: ...Geareducer model 32 2 INSTALLATION OPERATION MAINTENANCE Z0238997_C ISSUED 06 2022 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT user manual ...

Страница 2: ...dded via the filler neck or pumped in through the drain connection this lubricant will not reduce the overall level of protection however if the unit is operated for any amount of time the Pre Commission period is depleted and the unit is now considered to be in Operational status Check the Geareducer exterior yearly Touch up with paint as required Exposed pipe threads are coated to prevent corros...

Страница 3: ... of Geareducer and connecting oil line Also at this time observe the contact pattern of the gear teeth to see if they appear as illustrated in Detail A and B If incorrect gear tooth pattern should occur refer to Marley Field Repair Manual for Series 32 2 Geareducer operation and service Figure 1 Priming Interstage Shaft Check all gasketed joints for oil seepage Tighten cap screws and flange boltin...

Страница 4: ...4 Detail A Spiral Bevel Gear Tooth Pattern Detail B Helical Gear Tooth Pattern operation and service ...

Страница 5: ...n cover Full is the center of the sight glass If oil is not visable in the sight glass then oil needs to be added See Figures 3 and 4 Install plug 2 Start the fan drive and run for one minute 3 Stop the fan drive Allow ten minutes for oil level to stabilize and recheck oil level at the Geareducer 4 If necessary repeat steps 2 and 3 until stabilized oil level is at the proper level 5 Check gauge pl...

Страница 6: ...dd oil if required noting the addition in your maintenance log If equipped with an external dipstick oil level gauge small quantities of oil can be added at that location Semi annually If using turbine type mineral oil change oil see Changing Geareducer Oil for instructions Check that all the assembly bolts and cap screws are tight that oil plugs and pipe connections are in place and free from lea...

Страница 7: ...aul your Geareducer refer to the Field Repair Section and Geareducer Parts List Suggested Lubricants The following list of lubricants in Table 1 is provided as reference only These products have been recommended by their respective manufacturers as acceptable for use in a Marley spiral bevel and or helical Geareducer for cooling tower applications This list is not an attempt to include all the lub...

Страница 8: ...IES In the interest of technological progress all products are subject to design and or material change without notice Geareducer 32 2 US E R MAN UAL SPX COOLING TECH LLC 7401 WEST 129 STREET OVERLAND PARK KS 66213 USA 913 664 7400 spxcooling spx com spxcooling com ...

Отзывы: