Maintenance
Warning
Maintenance Instructions
Always make certain that mechanical equipment is inoperable during
periods of maintenance—or during any situation of possible endan-
germent to personnel. If your electrical system contains a disconnect
switch, lock it out until the period of exposure to injury is over.
The top of the tower is not a working surface. Do not stand, sit or
walk on top of the tower. Use an appropriate ladder adjacent to the
tower whenever you perform any maintenance activity on the tower’s
upper surfaces.
This product is constructed using cold-formed sheet metal. Use
protective clothing, gloves and shoes as appropriate for protection
against edges of thin gage material.
Motor
Lubricate the motor according to the motor manufacturer’s supplied in-
structions. Remove any oil, dust or scale deposits from the motor which
can cause excessive insulation temperatures.
Refer to
Electric Motors on Cooling Towers
, Manual 92-1475, for additional
maintenance and lubrication information.
Fan Shaft Bearing Housing
Check bearing housing oil cup level. Fill to the proper level with SAE 0
(ISO 100) weight oil.
Belt Tension
Check belt tension every two to three weeks during peak operating sea-
son.
Makeup Float Valve
Check float valve periodically for proper operation and proper water
level.
Basin and Suction Screen
Drain and clean cold water basin and suction screen periodically.
Blowdown
Check the blowdown for continuous water discharge during operation.