11 Tuning and maintenance
11.1.1.6 Modification of the configured parameters
A.
Press on the
PRG
button for more than 5 seconds.
The first modifiable parameter is shown on the display.
B.
Press on the
UP
and
DOWN
keys to specify the parameter that should be changed.
C.
Press on
SEL
to display the value of the selected parameter.
D.
Modify the value with the
UP/DOWN
keys until the desired value is displayed.
E.
Press on the
SEL
button again to store the new value and move on to display the following parameter.
F.
Press on the
PRG
key to store the new value and terminate the parameter modification procedures.
In order to exit without saving the values: just wait 60 seconds without doing anything to the ma-
chine.
The only parameter that the user is authorised to change is the differential regulator. The modi-
fication of any other parameter may affect the operation of the refrigeration unit in an inappro-
priate manner.
Marksa SA denies all responsibility for any un-authorised parameter modification.
Parameter
Symbol
Type
Min.
Max.
Units
Regulated
Differential regulator
F
0.1
+19.9
°C / °F
2
Table 11-1: Control setting parameters
Содержание CSSW 50
Страница 1: ...INDUSTRIAL REFRIGERATION UNITS TECHNICAL NOTICE V1 0...
Страница 8: ...Page 8 100 Technical Notice V1 0 01 09 Table of contents...
Страница 14: ...Page 14 100 Technical Notice V1 0 01 09 1 Introduction...
Страница 32: ...Page 32 100 Technical Notice V1 0 01 09 4 Model CSW 100 150...
Страница 38: ...Page 38 100 Technical Notice V1 0 01 09 5 Model CSW 200 300...
Страница 44: ...Seite 44 100 Technical Notice V1 0 01 09 6 Model CSW 400...
Страница 90: ...Page 90 100 Technical Notice V1 0 01 09 12 Options...
Страница 99: ...Technical Notice V1 0 01 09 Page 99 100 100 Appendix 14 14 5 Compliance documents...