8
OPERATING INSTRUCTIONS
CAUTION: BE SURE TO READ:
Disconnect The Power Supply to the boiler before servicing or cleaning.
Keep the appliance area free and clear of combustibles.
Do not obstruct the flow of combustion and ventilation air.
Keep this manual for future reference.
Contact the factory, the factory representative, or an authorized service company to perform
maintenance and repairs.
In the event of a power failure, no attempt should be made to operate the appliance. Be sure
the water switch is in the OFF position.
LIGHTING INSTRUCTION, SPARK PILOT:
(
Be sure boiler drain valve is closed
)
1.
Press water switch from OFF to ON.
2.
Wait 5 to 10 minutes for water to fill in the boiler (
Gauge glass should be 2/3 full
).
3.
Press the heat switch from ON to OFF and release back to ON position when the low water light
goes OFF. Green indicator light will come on (This is necessary to manually reset the unit).
ADJUSTMENTS
A. IF GAS PRESSURE IS LOW:
Check your gas supply line for a restriction. If no restriction exists, check with your Natural gas supplier
to provide at least 5” of water column pressure in the gas supply line. If no restriction exists and
Propane gas is being used, the tank pressure regulator should be adjusted to supply at least 11” of water
column pressure in the gas supply line. If this adjustment cannot be made to your satisfaction, the gas
supplier should be notified.
B. IF GAS PRESSURE IS TOO HIGH:
Adjust the pressure regulator on the boiler gas valve to reduce the pressure if Natural gas is being used.
If Propane gas is being used, adjust the pressure regulator supplied by the gas supplier. If the regulator
cannot be adjusted, notify the gas supplier.