8.3  Electrical connection condensate pump

Pump running time (standard)   

 

Pump float switch (special)

8.4 Mounting
The FBA Ultra must be installed absolutely horizontal or with a slight slope of 1mm for the 

condensate pump. 

8.5 Commissioning
Free the condensate tray of dust and other contaminants. Before commissioning the operation of 
the condensate pump must be checked. For this, remove the removable louvres, pour distilled water 
into the tray and remove the pump. Only after making sure that the pump is working properly, the 

device can be put into operation. 

8.6 Maintenance
Regularly (at least every six months) and before the cooling down period, the condensate tray must 
be subjected to a visual inspection. Existing deposits (dust, mud, vermin, etc.) must be removed.
For a correct operation of the pump, the round filter that is placed in the supply of the pump must 
be cleaned or replaced regularly. The frequency for cleaning and replacing the filter depends on the 
operating conditions. After an extended period, the filter must definitely be cleaned or if necessary 

replaced.

In the abscence of maintenace the warranty expires!

9 Maintenance

9.1 Warranty
Our warranty does not cover damage caused by improper use or maintenance. Moreover, 
experience shows that with increasing age of the products, lack of maintenance leads to greater 

damage. 

Inspections of the safety equipment should only be performed by trained and qualified personnel! 
Please contact the service department of your supplier.

2

U2

V2

V1

W1

T K

T K

P E

1

65

10

9

43

87

12

11

14

13

20

19

W2

U1

L1

N

18

17

24

23

16

15

22

21

Isolator switch

TK = Thermocontact

Y - Position: low speed

Engine 001
2 speeds, with isolator switch

bro

wn

 - Position: high speed

blue

blac

k

or

ang

e

red

brown

blue

blac

k

red

grey

whit

e

whit

e

Condensate pump

Float switch

Level switch emergency stop

50 VA ohmse load

(Alarm) 250 V

2

U2

V2

V1

W1

TK

TK

PE

1

5

6

9

01

3

4

7

8

11

21

31

41

91

02

W2

U1

L

N

71

81

32

42

51

61

12

22

L1

N

PL

PN

C

NC

Isolator switch

TK = Thermocontact

Y - Position: low speed

Engine 001
2 speeds, with isolator switch

brow

n

 - Position: high speed

blue

blac

k

orange

re

d

gre

y

whit

e

whit

e

ws

ws

ws

ws

Connection box

Float switch

brow

n

blue

Condensate pump

Содержание 0662551

Страница 1: ...Technical manual EN MARK TANNER FBA ULTRA 0662551...

Страница 2: ...2...

Страница 3: ...hat they do not play with the appliance Index 1 Intended use 4 2 Safety 5 3 Receiving of the goods 6 3 1 Damage in transport 6 3 2 Transport packaging 6 4 Mounting 6 4 1 Ceiling mounting 6 4 2 Mountin...

Страница 4: ...are suitable for Transport of air that is Dust free Without harmful substances Non agressive Non corrosive Not flammable Purification of air for Filtering Heating Cooling Consultation with or consent...

Страница 5: ...stopped The components have been cooled down to room temperature Note Only qualified personnel should perform maintenance on the electrical components Consider the local regulations Changes or additi...

Страница 6: ...4 1 Ceiling mounting Fastening the FBA device to the ceiling must be done with officially approved fasteners In the dimensioning of the fastening the following gear weights should be taken into accoun...

Страница 7: ...on the outside to prevent condensation 4 3 Roof mounting The mounting of roof accessories raincover or channels can be performed at the scene Slabs are not included 4 4 Louvre adjustment When adjustin...

Страница 8: ...heat exchanger When decommissioning the frost protection thermostat should be connected to the air outlet side of the heat exchanger 4 6 Air valve and drain valve When using an air valve you must mak...

Страница 9: ...ing unit 685 52 54 E TK Thermocontact TK Thermocontact Fan engine 1 Fan engine 2 o X TK Thermocontact TK Thermocontact Fan engine 1 Fan engine 2 o X Switching unit 685 55 58D 683 56D 58D 7 wire 7 wire...

Страница 10: ...5 685 55D 5 2 1 685 56D 10 4 2 685 57D 20 8 5 685 58D 35 14 10 5 wire 5 wire 9 wire 4 wire 4 wire 9 wire RT Room thermostat TK Thermocontact RT Room thermostat TK Thermocontact Location supply fuses...

Страница 11: ...ocontact Location supply fuses 1 U 2 U 11 685 54E 12 14 N L L RT RT 250 V AC max 2A 250 V AC max 1A RT FS FS TK TK L1 N FS TK M 1 1 U 2 U 11 685 52 53E 12 14 1 2 3 6 7 250 V AC max 2A 250 V AC max 1A...

Страница 12: ...ostat and actuator on off 517 Switching unit Position 0 Servomotor Position Closed Position 0 Servomotor Position Closed 13 14 21 22 13 14 21 22 707 OPEN CLOSE N 14 12 671 N 685 54 E 685 55 58 D 1 2 6...

Страница 13: ...will end the warranty of the engine Important switching capacity 10 A with cos 1 0 6 A with cos 0 6 Voltage 250 V Voltage power 2000 V eff If the engine protection is in operation the engine can only...

Страница 14: ...of engines switches and other electrical accessories should be done in accordance with the relevant standards VDE 0100 EMC act rules of RU For speed control a frequency converter cannot be used since...

Страница 15: ...ordance with the technical data The condensate pump lies in the drip tray In the inlet of the pump a round filter has been inserted See figure 2 The condensate pump is designed for continuous use For...

Страница 16: ...he filter must definitely be cleaned or if necessary replaced In the abscence of maintenace the warranty expires 9 Maintenance 9 1 Warranty Our warranty does not cover damage caused by improper use or...

Страница 17: ...the heat exchanger by blowing compressed air onto it Take care of oil containing dust with an oil soluble detergent Use a steam cleaner to remove sticky surface Note Use low pressure as well as an in...

Страница 18: ...g screws and remove the unit 8 Disassemble the rear wall after screws on position 4 4x position 3 3x and if necessary position 1 3x have been removed and remove the engine 9 Pull the heat exchanger fr...

Страница 19: ...er cables must be removed by a qualified electrician More over all fluid carrying parts must be completely empty This must be done by a professional company that properly draines the water with anti f...

Страница 20: ...ELGIQUE TELEFOON 32 0 3 6669254 FAX 32 0 3 6666578 info markbelgium be www markbelgium be MARK DEUTSCHLAND GmbH MAX PLANCK STRASSE 16 46446 EMMERICH AM RHEIN DEUTSCHLAND TELEFON 49 0 2822 97728 0 TELE...

Отзывы: