Maritime Geothermal nordic dx-45 Скачать руководство пользователя страница 31

Page .... 31 

Maritime Geothermal Ltd. 

12-Feb-00 

Theory of Operation 

 
The Nordic DX heat pump operates on the principle of a 

buried multi loop condenser / evaporator assembly to ex-
change energy to and from the earth as required by the sea-
son.  

 
When heating is required the heat pump uses all loops 

(typically 1 per ton) in parallel to extract heat from the 
ground. During the cooling mode when the buried loops are 
acting as a condenser, the number of loops in operation at any 
one time must be controlled in accordance with their tempera-
ture for proper operation of the heat pump. 

 
To accomplish this Maritime Geothermal Ltd. has de-

signed an electronic control board to monitor and control all 
aspects of the DX heat pump operation.  

 

The NORDIC CONTROLLER BOARD  (hereinafter 

called NCB) has been designed to operate the heat pump with 
the highest reliability and efficiency without the main micro-
processor being directly connected to the heat pump and it's 
associated AC noise which can cause erratic operation. We 
have isolated all INPUTS, OUTPUTS and the POWER SUP-
PLY from the AC supplies in the heat pump so that AC noise 
is not a problem.   

 
All the inputs for thermostat functions are optically cou-

pled to the  NCB where they are transferred to a +5v or 0v 
signal for the microprocessor. The NCB reads the voltage on 
each of it’s inputs and determines what functions are required 
based on this information. 

  

Thermostat INPUTS   

 
NOTE: The thermostat chosen should be a good quality 

2-stage heating, 1-stage cooling heat pump style thermostat. If 
the stat is a mercury bulb style unit the heating and cooling 
anticipators must be set completely out of the circuit so that 
they will not affect the run time of the DX heat pump 

By allowing the 24vAC thermostat to operate the con-

troller board instead of the heat pump’s controls directly we 
improve reliability in two ways: 

      1. The stat does not have to handle any current from 

compressor relays, loop solenoids etc. In our system, direct 
connection to the stat could put loads on the stat which would 
shorten it's life. With the 24v signal we send, only a few mili-
amps of current are required.  

      2. It is impossible to for the installer to short any-

thing during the installation of the thermostat. Crossed con-
nections etc. would only activate the compressor or blower 
etc. in some erratic manner but would not damage the control-

ler board. 

 
The NCB has all all the time delay functions of a con-

ventional electronic thermostat built into its program and all 
indicator lights function normally. 

 
The (8) terminals going to the thermostat from the NCB 

are as follows: 

3. G - indicates blower required 
2. B - indicates mode switch in (HEATING) 
5. Y - compressor operation required      
4. W - indicates (ELECTRIC HEAT) required 
6. O - indicates mode switch in (COOLING)        
7. L – Lock-out indicator light. 
1. R - has 24v hot signal continuously. 
1. C – common 
                                   
For example: When the mode switch (cool/off/heat/EM 

heat) is set to OFF the NCB does not see 24v on either "B" or 
"O" terminals and therefore knows the system is in the OFF 
position. 

 
If the NCB sees a signal on "B" it knows the mode 

switch is set to HEAT and will bring on the compressor when 
the thermostat is turned up and the thermostat makes a contact 
with the "Y" terminal. 

If there is no “B” terminal on your thermostat or if the 

unit is a DX-to-Water machine  

 
Similarly by moving the selector switch COOL, a 24v 

signal on the "O" terminal indicates that COOLING mode has 
been entered which activates the reversing valve, the NO liq-
uid line solenoid and 1 cooling loop. When "Y" is made by a 
contact closure of  the stat the compressor is activated. 

 
A 24v signal on "G" will activate the system fan (FAN 

switch set to "ON") 

 
A 24v signal appearing at "W"  (terminal  designated as 

second stage heating) during any time except when the 
MODE selector is in COOLING will bring on the supplemen-
tary heat. 

   
There are adjustable time delay's built into for every 

function that the NCB looks after. These time delays can be 
changed in the field by a serviceman with a laptop computer 
and a serial cable. (A list of printouts available from the NCB 
are included in appendix.) 

 
 

High & Low Pres. Controls and Loop 
Pressure  Limit Switch INPUTS 

 

NORDIC®  Electronic Control Board  

Содержание nordic dx-45

Страница 1: ...rouble Shooting Guide 24 Optimum Placement 7 Horizontal Dimensions 19 Electrical Schemetic 27 Instaling DX linesets 9 Electrical Requirements 20 Installer Wiring 28 Vacuuming Charging 11 Component Lay...

Страница 2: ...age 2 Maritime Geothermal Ltd 12 Feb 00 A NORDIC Direct Expansion Heat Pump System Energy Input Storage System Earth s Mass Extraction Heat Distribu NORDIC DX to Water NORDIC DX to Air HEATING COOLING...

Страница 3: ...d of installing a DX unit A high water table in the borehole area 20 to 30 ft will insure that there is adequate conduction with the earth and although the loop length per ton is shorter than the hori...

Страница 4: ...alled to pre vent the build up of pressure which may result in bursting of the circulator pump housing if the unit is operated while both valves are shut See point A marked above Nordic DX All Models...

Страница 5: ...10 times greater than a similar capacity conventional geothermal heat pump 4 Approximately 3 times as much refrigerant required in the cooling mode as is required in the heating mode 5 Lack of a prop...

Страница 6: ...nch to the basement wall Liquid lines must be insulated from the heat pump to approx 6 ft down the drop pipes in the vertical boreholes Install spacers to keep the pipes separated as far as possible f...

Страница 7: ...struction for a distance of 2 two ft so that servic ing and general maintenance can be carried out with a mini mum of difficulty Raising the heat pump off the floor a few inches is generally a good pr...

Страница 8: ...Page 8 Maritime Geothermal Ltd 12 Feb 00 Piping Layout of Vertical Style DX Heat Pump System 120 ft max 100 ft typical HOME...

Страница 9: ...above ground and entering the dwelling between the floor joists just below the first floor These pipes should be insu lated with a minimum of 3 4 of closed cell weatherproof in sulation There will be...

Страница 10: ...Page 10 Maritime Geothermal Ltd 12 Feb 00 NORDIC DX Horizontal Trench Design...

Страница 11: ...will be impossible and attempting to do so will introduce moisture to the system making the process take much longer to vacuum after the leak has been found and re paired Vacuum the system until the...

Страница 12: ...Page 12 Maritime Geothermal Ltd 12 Feb 00 NORDIC Horizontal DX Heat Pump System Plan View...

Страница 13: ...be kept below 2 inches of water total Return ducts should ideally be placed in every room and be sized 50 lar ger than corresponding supplies In some instances the num ber of floor diffusers will actu...

Страница 14: ...ld be a excavated area or an existing area which needs to be filled as part of general excavation Loops should be buried approxi mately 6 ft underground for best performance Example Nordic DX 45 shoul...

Страница 15: ...close at the same time The TX valves control the flow of liquid refrigerant to it s loop by virtue of the sensing bulbs being attached to each respective return vapor line and all the equalizer lines...

Страница 16: ...a sis as the field warms up 2 It allows the machine to switch from heating to cooling mode without shut off on it s low pressure control since refrigerant pressure is supplied to the intake of the com...

Страница 17: ...Page 17 Maritime Geothermal Ltd 12 Feb 00 NORDIC Series DX 45 55 65 Engineering and Performance Data June 1997...

Страница 18: ...binet is fully insulated with flame retardant accoustic material Supply Return Duct Sizes Basic cabinet design is the same for all DX models 45 55 65 Cold air return measures 27 x 30 5 Hot air plenum...

Страница 19: ...OOR SIZE 28 W x 31 H 1 25 1 00 31 00 1 00 4 22 4 00 3 50 3 50 4 50 7 50 5 00 5 00 33 00 17 13 6 99 RIGHT SIDE DOOR 26 07 2 50 BACK SIDE Return Air Side 19 00 Electric Box 1 00 18 00 DOOR Filter rack a...

Страница 20: ...18 18 Thermostat conductors 8 8 8 Disconnect Switch Thermostat Temperature IN F Temp OUT F Temperature Rise F of Total DX 45 Igal hr DX 55 Igal hr DX 65 Igal hr 40 150 110 20 10 11 8 14 5 45 150 105...

Страница 21: ...IN Domestic Hot Water OUT Bronze head Magneti cally driven Hot Water circulator High Low access ports Microprocessor con trolled operation Electronic thermostat Auto changeover from HEAT to COOL High...

Страница 22: ...LAT Diff Sens cooling Latent Cooling Total Cooling Comp Amps Comp Watts Blower Amps Blower Watts Total Watts EER Suct Disc Pres 50 80 2 52 7 27 5 38549 20002 58550 16 3 3490 3 4 341 3830 15 3 68 171...

Страница 23: ...0 110 6 40 8 76542 29 2 5990 4 3 415 6405 3 50 68 2 255 1 55 50459 71 108 5 38 0 70659 27 8 5721 4 2 413 6134 3 37 62 8 245 9 50 46511 70 105 7 35 7 67164 26 7 5428 4 1 414 5842 3 37 57 2 234 1 45 421...

Страница 24: ...ny Burned out motor Ohmmeter shows no resistance between common and run ter minals or between common and start terminals Note Be sure compressor overload has had a chance to reset If comp is hot this...

Страница 25: ...room comes up to tem perature Faulty low pressure ctrl Refrigerant pressure control should open on drop at approx 20 psig Control should reset automati cally Heat pump can then be restarted by resetti...

Страница 26: ...e at 120 F and open at 140 F Replace thermostat if faulty Disconnect switch open or fuse blown in electri cal supply to hot water tank Check both line and load sides of fuses If switch is open de term...

Страница 27: ...Page 27 Maritime Geothermal Ltd 12 Feb 00 NORDIC DX Series Schematic Wiring Diagram Package Unit Schemetic Shown...

Страница 28: ...rmostat sup plied C common G blower relay Y Y2 compressor R 24v hot supply L compressor lock out light O W2 reversing valve B heating mode Plenum Heater Connections use 18 4 t stat wire FF to FF in he...

Страница 29: ...ing 2 conductors con nect F and F in the heat pump s electrical box to F and F in the ple num heater A 18 4 wire Thermostat Operation The NORDIC heat pump comes sup plied with a 2 stage heating 1 stag...

Страница 30: ...20 16 x 17 16 5 x 16 5 20 1750 2000 18 8 x 40 10 x 30 12 x 24 14 x 20 16 x 17 16 5 x 16 5 22 2000 2250 20 10 x 38 12 x 30 14 x 26 16 x 22 18 x 19 18 5 x 18 5 22 2250 2600 20 10 x 38 12 x 30 14 x 26 16...

Страница 31: ...stat could put loads on the stat which would shorten it s life With the 24v signal we send only a few mili amps of current are required 2 It is impossible to for the installer to short any thing durin...

Страница 32: ...ommunica tion Port Activates loop 1 through 5 Cooling loop solenoids Soaker Hose E Emergency Heat O Reversing Valve G Blower Y Compressor R 24v Hot C Common 24vAC Low Pres Ctrl High Pres Ctrl Short Pi...

Страница 33: ...y coupled to solid state switches so that the worst malfunction in wiring etc would produce only minor damage if at all to the output section of the control board There are 12 output connections at th...

Страница 34: ...will activate followed by the blower If the system has been in the HEAT mode there will be a delay as the MODE switch timer keeps the compressor OFF for 5 minutes adjustable The compressor will start...

Страница 35: ...Page 35 Maritime Geothermal Ltd 12 Feb 00...

Страница 36: ...Data Sheet have it en dorsed by the owner and return it to Maritime Geothermal Ltd within 21 days after the installation of the unit 3 It is the responsibility of the building or general contractor to...

Отзывы: