![Maritime Geothermal nordic dx-45 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/maritime-geothermal/nordic-dx-45/nordic-dx-45_installation-manual_1727432026.webp)
Page .... 26
Maritime Geothermal Ltd.
12-Feb-00
Fault
Possible Cause
Verification
Recommended Action
Low or “no” air
conditioning
Open control circuit
Thermostat not set to signal
operation
Turn room thermostat down.
Reduced air flow or re-
turn air temperature too
cold. Unit trips out on
low suction pressure
control.
Check for:
1. Dirty air filter.
2. Fan belt slipping.
3. Broken blower belt.
4. Inoperative blower motor.
1. Replace filter
2. Tighten blower belt.
3. Replace belt.
4. Replace blower motor.
Insufficient hot
water
Circulator pump not op-
erating.
Visually inspect the pump to
see if shaft is turning. Use an
amprobe to measure current
draw.
Replace if faulty.
Blockage or restriction
in the water line or hot
water heat exchanger.
Check water flow and power
to pump. Check water lines for
obstruction
Remove obstruction in water
lines. Acid treat the domestic
hot water coil.
Thermostat limit is
open.
Check contact operation.
Should close at 120°F and
open at 140°F.
Replace thermostat if faulty.
Disconnect switch open,
or fuse blown in electri-
cal supply to hot water
tank.
Check both line and load sides
of fuses. If switch is open de-
termine why.
Replace blown fuse or breaker
or close switch.
Reset button tripped on
hot water tank.
Check voltage at elements
with multimeter.
Push reset button.
Thermostat on hot water
tank set too low. Should
be set at 120°F.
Visually inspect the setting.
Readjust the setting to 120°F.
Heat pump not running
enough hours to make
sufficient hot water.
Note the amount of time the
heat pump runs in any given
hour.
Temporarily turn up the tank
thermostats until colder
weather creates longer run cy-
cles.
In-line Flowmeter
Digital Thermometer
Refrigeration Gauges
Amprobe
Trouble Shooting Tools
The Dole® flow control is a simple, self-
cleaning device designed to deliver a con-
stant volume of water from any outlet
whether the pressure is 15 psig or as high as
125 psi. The controlling mechanism consists
of a flexible orifice that varies it’s area in-
versely with pressure so that a constant flow
is maintained.
Dole flow control Valve
Содержание nordic dx-45
Страница 10: ...Page 10 Maritime Geothermal Ltd 12 Feb 00 NORDIC DX Horizontal Trench Design...
Страница 12: ...Page 12 Maritime Geothermal Ltd 12 Feb 00 NORDIC Horizontal DX Heat Pump System Plan View...
Страница 17: ...Page 17 Maritime Geothermal Ltd 12 Feb 00 NORDIC Series DX 45 55 65 Engineering and Performance Data June 1997...
Страница 35: ...Page 35 Maritime Geothermal Ltd 12 Feb 00...