2.4.3  Checking Connections 

Once the NMEA 2000

® 

connection and switch connection(s) to the SIM100 have been 

completed, check to see that information is being properly transmitted by observing an 
appropriate NMEA 2000

®

 display.  If you don’t see switch indicator status, refer to Section 5, 

“Troubleshooting”. 
 

2.5  Configuring the SIM100 

The SIM100 will transmit data over the NMEA 2000 network as it is shipped from the factory; 
however, it may require configuration, depending on the type of switch monitored. There are 
several configurable items within the SIM100, which are detailed in the remainder of this 
section. 
 
You configure the SIM100 using a Maretron DSM250 display or other NMEA 2000

®

 display 

unit that is capable of configuring the SIM100. Please refer to the Maretron 

DSM250 User’s 

Manual

 for details. 

 

2.5.1  Device Instance 

NMEA 2000

®

 provides a unique device instance for each switch monitoring device on a vessel. 

This value should be programmed in each SIM100 so that each SIM100 is associated with a 
unique device instance number. The default instance number is 0, which is used to indicate the 
first SIM100 that is hooked to the network. Subsequent SIM100s connected to the network 
would be numbered 1, 2, and so on. 
 

2.5.2  Channel #1 Mode 
2.5.3  Channel #2 Mode 
2.5.4  Channel #3 Mode 
2.5.5  Channel #4 Mode 
2.5.6  Channel #5 Mode 
2.5.7  Channel #6 Mode 

You must configure the SIM100 as to what type of switch circuit it is monitoring. The allowable 
values for this parameter are as follows: 
 

  “End of Line Resistor” (default) – The switch circuit has a SPST switch connecting the A 

and B terminals, with a parallel 8 K

 end-of-line resistor. This allows the SIM100 to 

monitor the circuit and indicate an error condition if the monitored circuit somehow 
becomes disconnected from the terminals on the SIM100. 

  “No End of Line Resistor” – The switch circuit has a SPST switch connecting the A and 

B terminals, with a no parallel end-of-line resistor. The SIM100 is not able to monitor the 
circuit for disconnection in this case. 

  “Disable” – Use this value if no switch circuit is connected to the corresponding switch 

terminals.  The SIM100 will indicate that no data is available for this circuit. 

 

Содержание SIM100

Страница 1: ...age i SIM100 Switch Indicator Module User s Manual Revision 1 0 Copyright 2008 Maretron LLP All Rights Reserved Maretron LLP 9014 N 23rd Ave 10 Phoenix AZ 85021 7850 http www maretron com Maretron Manual Part M001801 ...

Страница 2: ...SIM100 User s Manual Page ii Revision 1 0 Revision History Revision Description 1 0 Original document ...

Страница 3: ...el 1 Mode 6 2 5 3 Channel 2 Mode 6 2 5 4 Channel 3 Mode 6 2 5 5 Channel 4 Mode 6 2 5 6 Channel 5 Mode 6 2 5 7 Channel 6 Mode 6 2 5 8 Advanced Configuration 7 2 5 9 NMEA 2000 PGN Enable Disable 7 2 5 10 Restore Factory Defaults 7 3 Maintenance 7 4 Troubleshooting 7 5 Technical Specifications 9 6 Technical Support 10 7 Installation Template 11 8 Maretron 2 Year Limited Warranty 12 Table of Figures F...

Страница 4: ......

Страница 5: ...f the monitored device is so equipped With the SIM100 you can rest assured that critical sensors are receiving power signal wires are connected and all the safety security and vessel functions are under constant supervision The Maretron SIM100 is designed to operate within the harsh demands of the marine environment However no piece of marine electronic equipment can function properly unless insta...

Страница 6: ...tion Section 2 2 3 Mount the SIM100 Section 2 3 4 Connect the SIM100 Section 0 5 Configure the SIM100 Section 2 5 2 Installation 2 1 Unpacking the Box When unpacking the box containing the Maretron SIM100 you should find the following items 1 SIM100 Switch Indicator Module 1 Parts Bag containing 4 Stainless Steel Mounting Screws 1 SIM100 User s Manual 1 Warranty Registration Card If any of these i...

Страница 7: ...he NMEA 2000 connector is a round five pin male connector see Figure 2 You connect the SIM100 to an NMEA 2000 network using a Maretron NMEA 2000 cable or compatible cable by connecting the female end of the cable to the SIM100 note the key on the male connector and keyway on the female connector Be sure the cable is connected securely and that the collar on the cable connector is tightened firmly ...

Страница 8: ...itch 1 Signal B 3 SW2A Switch 2 Signal A 4 SW2Bl Switch 2 Signal B 5 SW3Al Switch 3 Signal A 6 SW3B Switch 3 Signal B 7 SW4A Switch 4 Signal A 8 SW4B Switch 4 Signal B 9 SW5A Switch 5 Signal A 10 SW5B Switch 5 Signal B 11 SW6A Switch 6 Signal A 12 SW6B Switch 6 Signal B Before attempting to connect the SIM100 to the AC source determine the type of system you will be monitoring The SIM100 supports ...

Страница 9: ...red switch to switch channel 1 via the termin named SW1A and SW1B Connections to other switch terminals are similar 8 KΩ end of 2 Please refer to Figure 4 for connecting the SIM1 This figure shows the connection of the monitored switch to switch channel 1 via the terminals named SW1A and SW1B Connections to other switch terminals are similar 1 2 5 4 3 6 7 8 9 10 11 12 2B SIM100 Screw Terminals SW1...

Страница 10: ... so that each SIM100 is associated with a unique device instance number The default instance number is 0 which is used to indicate the first SIM100 that is hooked to the network Subsequent SIM100s connected to the network would be numbered 1 2 and so on 2 5 2 Channel 1 Mode 2 5 3 Channel 2 Mode 2 5 4 Channel 3 Mode 2 5 5 Channel 4 Mode 2 5 6 Channel 5 Mode 2 5 7 Channel 6 Mode You must configure t...

Страница 11: ... they may remove paint or markings or may corrode the SIM100 enclosure or seals Ensure that the unit is mounted securely and cannot be moved relative to the mounting surface If the unit is loose tighten the mounting screws Check the security of the cable connected to the NMEA 2000 connector and tighten if necessary Check the security of all of the switch connections on the top of the unit and tigh...

Страница 12: ...etween the A and B terminals for the appropriate indicator If the switch is open the resistance should either be an open circuit if the indicator is configured as No End of Line Resistor or should measure 8 KΩ if the indicator is configured as End of Line Resistor If the switch is closed the resistance should be close to 0 Ω A switch indicator always reads Open Ensure that the switch is connected ...

Страница 13: ...r Group Numbers PGNs Description PGN PGN Name Default Rate Periodic Data PGNs 127501 Binary Switch Bank Status 1 time 15 seconds and on switch change Response to Requested PGNs 126464 PGN List Transmit and Receive N A 126996 Product Information N A 126998 Configuration Information N A Protocol PGNs 059392 ISO Acknowledge N A 059904 ISO Request N A 060928 ISO Address Claim N A 065240 ISO Address Co...

Страница 14: ...echnical support for Maretron products you can reach us in any of the following ways Telephone 1 866 550 9100 Fax 1 602 861 1777 E mail support maretron com World Wide Web http www maretron com Mail Maretron LLC Attn Technical Support 9014 N 23rd Ave Suite 10 Phoenix AZ 85021 USA ...

Страница 15: ...Please check the dimensions before using the following diagram as a template for drilling the mounting holes because the printing process may have distorted the dimensions Figure 5 Mounting Surface Template Revision 1 0 Page 11 ...

Страница 16: ...ASE WILL MARETRON BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES DAMAGES FOR LOSS OF USE LOSS OF ANTICIPATED PROFITS OR SAVINGS OR ANY OTHER LOSS INCURRED BECAUSE OF INTERRUPTION OF SERVICE IN NO EVENT SHALL MARETRON S AGGREGATE LIABILITY EXCEED THE PURCHASE PRICE OF THE PRODUCT S INVOLVED MARETRON SHALL NOT BE SUBJECT TO ANY OTHER OBLIGATIONS OR LIABILITIES WHETHER ARISING OUT OF BREACH OF CON...

Страница 17: ... switch is closed Open The monitored switch is open Error There is an open connection between the SIM100 and the monitored switch This state can occur only when the indicator is configured to use an End of Line Resistor Data Not Available The indicator is configured as Disabled 3 Indicator 2 This field indicates the state of the switch connected to the SW2A and SW2B inputs of the SIM100 4 Indicato...

Отзывы: