ENGLISH 

SIN.NT.015.6 – M40FA640A/A 

Issued 04.2010 

USE OF POTENTIOMETERS

VOLT - potentiometer to change the output voltage of
the generator: 
Normally the internal potentiometer VOLT allows possibility 
of adjusting the voltage in a wide range (i.e. between 200 
and 560 V); to obtain a finer possibility of voltage setting or 
to adjust the voltage from the control panel, or in order to 
limit the voltage range, an external potentiometer can be 
connected to the terminal “P” and “Q” (resistance about 
100kOhm, 500mW, to /- 5% voltage regulation). 

 increases voltage 

FREQ - potentiometer to change the low speed 

 

protection:
usually it is set at the factory in order to reduce the 
excitation when speed becomes lower than 90% of rated 
speed at 50 Hz. By removing  the bridge which normally 
shorts the terminals “Hz” and “60”, the speed protection 
acts properly for 60 Hz operation.  
By acting on potentiometer FREQ it is possible to adjust 
further (in case should it be necessary) the frequency at 
which the low-speed protection is effective. 

 decreases frequency of intervention 

AMP - potentiometer to change the over-excitation 
limiter:
it permits to set the excitation voltage threshold of the over-
excitation limiter. 
The default setting of this potentiometer is at the maximum 
excitation voltage threshold. 

 increases the over excitation threshold. 

STAB - potentiometer to change stability:
by rotating it clockwise stability increases, but response 
time becomes larger. 

 increases response time, increases stability 

SLOPE - potentiometer to change the low speed 

 

protection characteristic slope:
with the micro-switch 4 OFF, this potentiometer allows to 
increase or decrease the under speed ramp slope, and set 
the voltage droop for a fixed reduced speed. 

 decreases the voltage droop for a fixed frequency 

intervention. 

PAR - potentiometer to change the droop
This potentiometer allows to change the voltage droop in 
load conditions. 

 the droop increases 

Содержание M40FA640A/A MARK I

Страница 1: ...M40FA640A A Mark I User Manual Automatic Voltage Regulator for Three phase Synchronous Generators Issued 04 2010 SIN NT 015 6...

Страница 2: ...Page 1 Instruction Manual Instal l ati on Op er ation Maintenance hanada technology Co Ltd MARELLI AVR M40FA640A...

Страница 3: ...rovided with the generator Should further information be required please contact After Sales Department see the reference at the end of the page SAFETY PRECAUTIONS WARNING when the regulation device i...

Страница 4: ...ration DATI TECNICI TECHNICAL DATA 0 5 a regime per valori di tensione e carico nominali REGULATION ACCURACY steady state conditions for rated Voltage and PF 0 5 variazione di tensione per variazione...

Страница 5: ...peration on regulator as replacement connection to accessories setting up extremely simple POWER STAGE INPUT TERMINALS U N terminals for power supply VOLTAGE SENSING INPUT TERMINALS S1 S2 S3 S4 S5 S6...

Страница 6: ...s a live part UNDERFREQUENCY LIMITER The regulator is provided with internal circuits in order to reduce the excitation when running at low speed in order to avoid damages to the excitation system of...

Страница 7: ...ications The stability of the regulator can be set on field to adapt it to the characteristics of the plant and or the driving engine diesel engine water turbine gas turbine in order to obtain the bes...

Страница 8: ...lleled with the grid an over excitation condition detected by the limiter can lead to a generator excitation shutdown with risk of loss of synchronism LIMITER SETTING for a quicker limiter setting it...

Страница 9: ...By acting on potentiometer FREQ it is possible to adjust further in case should it be necessary the frequency at which the low speed protection is effective decreases frequency of intervention AMP po...

Страница 10: ...to della limitaz Only for quick setting of the excitation limiter it permits to disable the normal limiter time delay Micro switch 4 ON OFF Protezione bassa frequenza con pendenza V f tarabile fare an...

Страница 11: ...10 ENGLISH SIN NT 015 6 M40FA640A A Issued 04 2010 12 TERMINALS AUX WINDING...

Страница 12: ...11 ITALIANO ENGLISH SIN NT 015 6 M40FA640A A Issued 04 2010 12 TERMINALS OVER EXCITATION DEVICE...

Страница 13: ...12 ITALIANO ENGLISH SIN NT 015 6 M40FA640A A Issued 04 2010 6 TERMINALS OVER EXCITATION DEVICE...

Страница 14: ...13 ITALIANO ENGLISH SIN NT 015 6 M40FA640A A Issued 04 2010 6 TERMINALS AUX WINDING...

Отзывы: