MarelliGenerators M40FA640A/A MARK I Скачать руководство пользователя страница 6

ENGLISH 

SIN.NT.015.6 – M40FA640A/A 

Issued 04.2010 

CONTROL TERMINALS

“Hz”, “60” : terminals for changing the low speed protection 
terminals 
“P”, “Q” : terminals for connection of external trimmer 
(100kOhm). 
“6”, “8”: input  terminals  for connections of external control 
systems (input for D.C. voltage , +/-3  Vdc).  The  terminal       
“         ” is to be used only in case of special connections. 

TERMINALS for interconnecting with over-boosting 
excitation systems 

“+”, “-” : output terminals (positive, DC, and negative, DC) 
“9” : voltage sensing 

EXTERNAL POTENTIOMETER

At the terminals “P” and “Q” an external trimmer (minimum 
rating 500mW, resistance about 100kOhm) can be 
connected. By acting on such trimmer, it is possible to 
obtain a voltage regulation of about +/- 5 % around the 
nominal voltage. By using a 200kOhm potentiometer it is 
possible to obtain a voltage regulation of about +/- 10 %.  
The trimmer is connected anyway (through the regulator) to 
the output of the generator and then it represents a live 
part. 

UNDERFREQUENCY LIMITER

The regulator is provided with internal circuits in order to 
reduce the excitation, when running at low speed, in order 
to avoid damages to the excitation system of the generator 
(i.e. to the regulator, to the exciter field, to the rotating 
rectifier, main rotor).  

The potentiometer “FREQ” fixes the corner-frequency, that 
is the frequency at which the limiter operates. Below that 
particular frequency, red LED switches-on and the voltage 
of the generator reduces further with speed reduction. 

By setting the micro-switch nr. 4 in OFF position, the 
voltage reduction is smaller and is close to be proportional 
to the speed reduction (voltage reduction is settable by the 
potentiometer ”SLOPE”). 

ANALOGUE INPUT 

The AVR accepts a voltage analogue input of +/-3Vdc 
maximum, to control the exciter field of the generator. 

This input has to be applied to terminals 6 and 8. 

In case of single operation, a maximum change of +/-3Vdc 
of the analogue input leads to a maximum change of +/-
25% of the generator voltage, with respect to the rated 
generator voltage.  
A value of 0Vdc does not lead to any change in excitation. 

Содержание M40FA640A/A MARK I

Страница 1: ...M40FA640A A Mark I User Manual Automatic Voltage Regulator for Three phase Synchronous Generators Issued 04 2010 SIN NT 015 6...

Страница 2: ...Page 1 Instruction Manual Instal l ati on Op er ation Maintenance hanada technology Co Ltd MARELLI AVR M40FA640A...

Страница 3: ...rovided with the generator Should further information be required please contact After Sales Department see the reference at the end of the page SAFETY PRECAUTIONS WARNING when the regulation device i...

Страница 4: ...ration DATI TECNICI TECHNICAL DATA 0 5 a regime per valori di tensione e carico nominali REGULATION ACCURACY steady state conditions for rated Voltage and PF 0 5 variazione di tensione per variazione...

Страница 5: ...peration on regulator as replacement connection to accessories setting up extremely simple POWER STAGE INPUT TERMINALS U N terminals for power supply VOLTAGE SENSING INPUT TERMINALS S1 S2 S3 S4 S5 S6...

Страница 6: ...s a live part UNDERFREQUENCY LIMITER The regulator is provided with internal circuits in order to reduce the excitation when running at low speed in order to avoid damages to the excitation system of...

Страница 7: ...ications The stability of the regulator can be set on field to adapt it to the characteristics of the plant and or the driving engine diesel engine water turbine gas turbine in order to obtain the bes...

Страница 8: ...lleled with the grid an over excitation condition detected by the limiter can lead to a generator excitation shutdown with risk of loss of synchronism LIMITER SETTING for a quicker limiter setting it...

Страница 9: ...By acting on potentiometer FREQ it is possible to adjust further in case should it be necessary the frequency at which the low speed protection is effective decreases frequency of intervention AMP po...

Страница 10: ...to della limitaz Only for quick setting of the excitation limiter it permits to disable the normal limiter time delay Micro switch 4 ON OFF Protezione bassa frequenza con pendenza V f tarabile fare an...

Страница 11: ...10 ENGLISH SIN NT 015 6 M40FA640A A Issued 04 2010 12 TERMINALS AUX WINDING...

Страница 12: ...11 ITALIANO ENGLISH SIN NT 015 6 M40FA640A A Issued 04 2010 12 TERMINALS OVER EXCITATION DEVICE...

Страница 13: ...12 ITALIANO ENGLISH SIN NT 015 6 M40FA640A A Issued 04 2010 6 TERMINALS OVER EXCITATION DEVICE...

Страница 14: ...13 ITALIANO ENGLISH SIN NT 015 6 M40FA640A A Issued 04 2010 6 TERMINALS AUX WINDING...

Отзывы: