Likely Cause

:

Corrective Action:

F.

Motor miswired at terminal box.

Match motor lead wiring to nameplate connection diagram.

G. Uneven, weak or loose mounting support.

Shim, strengthen or tighten where required.

H. Motor bearings defective.

Test motor by itself.

•  If bearings are bad, you will hear noise or feel roughness. Roller bearings 

are normally noisy when operated without load, limit roller bearing no load 

run time to five minutes.

•  If sleeve bearing, add oil per nameplate instructions. For motors with 

regreasing provisions, add grease per relubricating instructions

 (see 

section 7.5).

•  If noise persists contact warranty service.

I.

Motor out of balance.

1.  Disconnect from load.

2.  Set motor on rubber pads on solid floor.

3.  Secure a ½ height key in shaft keyway and energize from balanced power 

supply at rated voltage.

4.  Record vibration levels and compare with appropriate standards.

      If excessive vibration persists contact motor manufacturer.

Bearings repeatedly fail

A.

Load to motor may be excessive or 

unbalanced.

1.  If belt drive check system per section 4.3.2.

2.  Other than belting, check loading on motor shaft. An unbalanced load will 

also cause the bearings to fail. 

3.  Check runouts of mating components, such as a C-face and pump flange.

B.

Bearings contaminated.

Motor enclosure not suitable for environment. Replace with correct 

enclosure construction.

C.

Incorrect grease or bearings for 

ambient extremes. 

See Section 7.3 (Grease types). 

D.

VFD bearing damage.

Ground brush, common mode filter, or insulated bearings must be added. 

Contact motor manufacturer.

Motor at start up, makes a loud rubbing, grinding, or squealing noise

A. Contact between rotating and stationary 

components. 

Belt squeal during across the line starting is normal:

1.  CAUTION! 

Verify that supply voltage is within limits 

(see section 4.6).

2.  Ensure that motor lead wiring matches nameplate connection diagram:

3.  Isolate motor from load.

4.  To locate point of contact turn motor shaft by hand. 

5.  If point of contact is not located contact motor service shop. 

Start capacitors repeatedly fail

A. The motor acceleration time is too long.

Motor may be too small for load. Record acceleration time. Start 

capacitors may fail if acceleration time exceeds 3 seconds.

B. Motor is being started too frequently.

Excessive starting will damage motor capacitors. Contact motor 

manufacturer if motor is started more than 20 times/hour or if acceleration 

time exceeds 3 seconds. 

C. Motor voltage low.

CAUTION! 

Verify that voltage at the motor terminals is within limits

 (see 

section 4.6).

D. Defective start switch inside motor. 

Motor internal switch failure overheats start capacitor. Contact service 

shop or motor manufacturer.

Run capacitor fails

A. High ambient temperature.

Verify that the ambient does not exceed motor’s nameplate value.

B. Input voltage exceeds limit.

CAUTION! 

Verify that voltage at the motor terminals is within limits

 (see 

section 4.6).

C.

Power surge to motor (caused by 

lightning strike or other high transient 

voltage).

If a common problem, install surge protector.

 

Содержание REGAL TerraMAX

Страница 1: ...TerraMAX LOW VOLTAGE INDUSTRIAL MOTORS INSTALLATION OPERATION MAINTENANCE SAFETY MANUAL...

Страница 2: ...tial Inspection 03 3 2 Handling 03 3 3 Storage 04 4 0 INSTALLATION 04 08 4 1 Surroundings 04 4 2 Mounting 04 4 2 1 Rigid base footed 04 4 2 2 Vertical Mounting 04 4 3 Application assembly to the motor...

Страница 3: ...unused shaft keys and loose rotating parts to prevent them from flying off WARNING ROTATING PARTS HAZARD Keepextremities hair jewelryandclothingawayfrommovingparts 2 3 ENVIRONMENTAL SAFETY WARNING HAZ...

Страница 4: ...under the motor feet The number of shims used should be kept as low as possible i e stack as few as possible For special isolation mounting contact manufacturer for assistance 4 2 2 VERTICAL MOUNTING...

Страница 5: ...force should be at the midpoint of the shaft and it is good engineering practice to mount the motor pulley with hub and locking screw at the shaft end NOTICE BEARING FAILURE During assembly do NOT fo...

Страница 6: ...r the same zone protection method s and temperature code 4 5 2 SUPPLYTERMINALS Supply terminals are located in the terminal box They are suitable for receiving crimped lugs on the supply cables In add...

Страница 7: ...application may result in premature brake failure that results in minor moderate injury CAUTION BRAKE SOLENOIDWIRING Do NOT connect the brake solenoid to the output of aVFD The brake solenoids must be...

Страница 8: ...ification If an Adjustable Speed Drive is used on Ex nA motor follow the instructions on additional nameplate for converter supply in respect to applied load and frequency Check that the running curre...

Страница 9: ...se types When re greasing bearings ensure that the correct type of grease is used If in doubt about the existing grease type clean out the old grease thoroughly from bearings and bearing housing prior...

Страница 10: ...6317 NU317 85 38 1500 750 4000 2000 7000 3500 7000 3500 6318 NU318 90 45 1000 500 3000 1500 5000 2500 5000 2500 6319 NU319 95 45 1000 500 3000 1500 5000 2500 5000 2500 6322 NU322 110 60 3000 1500 500...

Страница 11: ...L 17 0115X DEMKO 17 ATEX 1967X Regal Beloit Asia Pte Ltd 12 Tuas Loop SINGAPORE II 3 G Ex nA IIC T3 Gc IP55 II 3 D Ex tc IIIC T135 Dc IP66 II 3 G Ex ec IIC T3 Gc IP55 IECEx UL 17 0129X DEMKO 17 ATEX 1...

Страница 12: ...become severely unbalanced 6 Replace fuse or reset circuit breaker Allow motor to cool down before resetting manual protector on motor WARNING Check automatic and manual reset protector warnings see...

Страница 13: ...ficient Air Flow TEAO Totally Enclosed Air Over motors Measure airflow next to motor surface and obtain minimum requirements from motor manufacturer E Motor is started too frequently Do not start more...

Страница 14: ...se or bearings for ambient extremes See Section 7 3 Grease types D VFD bearing damage Ground brush common mode filter or insulated bearings must be added Contact motor manufacturer Motor at start up m...

Страница 15: ...15 2019 2020 Regal Beloit Corporation All Rights Reserved MCIM2022E Form SB0250E NOTES...

Страница 16: ...Fernandez T 2108 Finsa 1 Santa Catarina Nuevo Leon Mexico 66350 T 01 800 84 73425 contacto regalbeloit com NEW ZEALAND Regal Beloit New Zealand Limited 18 Jomac Place Avondale Auckland New Zealand T 6...

Отзывы: