21
4.2 Turning the UPS On / Off
4.2.1
Start-up Procedure
CAUTION!
Ensure proper grounding connections!
◆
Turn ON the power switch for standard models.
◆
Turn the Battery Breaker “ON” for long backup time models.
CAUTION!
Endure the load is safely connected to the output of the UPS. If the
load is not ready to receive power, ensure that it is safely isolated
from the UPS output terminals.
◆
Turn ON the UPS input breaker
If the Rectifier input is within acceptable the voltage range, the rectifier will start up in
30 seconds after which the inverter will start up.
◆
Turn ON the UPS output breaker
When the inverter starts up, the UPS will transfer from bypass mode to inverter mode,
and then the bypass LED extinguishes, and the inverter LED Illuminates. If the rectifier
fails at startup, the bypass LED will illuminate. UPS status will be displayed on the LCD
panel.