Recommended cable sizing is as follows
:
UPS
Cable Sizing
AC Input
AC Output
DC Input
Grounding
10kVA
8 AWG
8 AWG
6 AWG
8 AWG
15kVA
6 AWG
6 AWG
2*6 AWG
6 AWG
20kVA
4 AWG
4 AWG
2*6 AWG
4 AWG
CAUTION!
Protective ground cable: Connect each cabinet to the main ground
system. For Grounding connection, follow the shortest route possible.
WARNING!
Failure to follow adequate grounding procedures may result in electro-
magnetic interference or electric shock and/or fire hazards.