background image

 
 

10 

SMS Server Software

 allows the card to communicate with an SMS Server, enabling 

event notifications to be sent via SMS messaging. Please contact Marathon Power at 

[email protected]

 for the latest version of this software. 

 
To open rar files for free, please install 7-zip on your computer, available at 

https://www.7-zip.org/download.html

  

 

After installing 7-zip, you maybe give options for using the program, choose File 

Manager. 

 

After clicking on the rar file, 7-zip opens. At this point, click on Extract on the upper 

lefthand side of the Toolbar. Then save the extracted exe file to your preferred location. 

  

 

Содержание SNMP Series

Страница 1: ...SNMP Card User s Manual for the SNMP CY54 03 and SNMP CY54 04 SNMP Cards ...

Страница 2: ...2 ...

Страница 3: ...oftware from our website 9 Netility 9 SNMPView 9 iMConfig 9 ClientMate 9 SMS Server Software 10 SNMP card UPS Installation 11 LED Indications on the card 12 Connecting to the SNMP cards 13 Connecting to the SNMP CY54 03 Card 13 Connecting to the SNMP CY54 04 Card 13 Configuration of the SNMP Cards 14 1 Configuration Network 14 2 Configuration SNMP Uniquely Identifying Your UPS 15 3 Configuration E...

Страница 4: ... Battery Status 27 Event Log and Event Timer Only Available on the CY54 04 Model 27 Summary Only Available on the CY54 04 Model 27 Contact Status Only Available on the CY54 04 Model 27 Remote Control 28 UPS Testing 28 Miscellaneous Control Commands Only Available on the CY54 03 Model 28 Dry Contact Status and Configuration Only Available on the CY54 04 Model 28 Meter Chart Only Available on the CY...

Страница 5: ...Y54 04 Model 34 Battery Charging Temperature Compensation 34 Battery Voltage Low Warning 34 External Fan On Off by Temperature 34 Battery Test Options 34 Inverter On Off Load Output ONLY 34 Reset the Event Timer Counters 34 Change Password 34 Transfer Points Only Available on the CY54 04 Model 35 Transfer Point Descriptions CY54 04 Model 36 Default Transfer Point Settings CY54 04 Model 37 Rebootin...

Страница 6: ...ions CY54 03 Model 44 Event Notifications CY54 04 Model 44 Emailing of Daily Report 45 Notifications Sent as SMS Notifications 46 SMS Server 47 Web Telnet FTP Security Settings 48 RADIUS Server Settings 49 System Time 50 Rebooting the Card 50 Language 51 Log Information Tab 52 Event Log 52 Data Log 52 Battery Test Log Only Available on the CY54 03 Model 52 UPS Event Log Only Available on the CY54 ...

Страница 7: ...7 Help 53 Save Restore Settings 53 Firmware Update Settings 54 Updating the CY54 03 Card s Firmware Important Note 54 Updating the CY54 04 Card s Firmware Important Note 54 About 55 Password Recovery 56 ...

Страница 8: ...anagement and configuration via Web Browser or NMS SNMPv1 SNMPv2C and SNMPv3 Supported TRAP email and SMS messages for events notifications Automatically emailing of Daily Reports Supports SNMP MIB for monitoring control Autosensing of Fast Ethernet 10M 100M Can gracefully shut down computers and servers after installing the ClientMate software Web Enabled The card creates a portal for the UPS tha...

Страница 9: ...athon power com s Netility rar SNMPView is an NMS software program used to monitor and control multiple cards With SNMPView you can view a UPS s location output status mode battery capacity AC status battery status and other parameters of all your UPSs all in one window Plus you can perform self tests send history files and more Download it at https marathon power com s SNMPView v58 rar iMConfig i...

Страница 10: ...est version of this software To open rar files for free please install 7 zip on your computer available at https www 7 zip org download html After installing 7 zip you maybe give options for using the program choose File Manager After clicking on the rar file 7 zip opens At this point click on Extract on the upper lefthand side of the Toolbar Then save the extracted exe file to your preferred loca...

Страница 11: ... SNMP card UPS Installation Find the correct SLOT on the UPS and remove the panel Align the card in the slot and gently push it in Reattach the screws to secure it in place Connect a LAN cable Turn ON UPS ...

Страница 12: ...f The card 9 Status Red Off Flashing Flashing UPS Communication Green On On On Power RJ45 Port Green On Flashing 100 Mbps Sending Receiving Data Yellow On Flashing 10 Mbps Sending Receiving Data LED Status NOTE When loading firmware the red LED alternating flashes DO NOT remove the card from the UPS ...

Страница 13: ...ge your computer s IP address to 192 168 1 2 Subnet Mask 255 255 255 0 Default Gateway 192 168 1 1 After making the connections above open any web browser and enter 192 168 1 254 into the address bar The SNMP CY54 03 does not require entering a username and password Connecting to the SNMP CY54 04 Card The SNMP CY54 04 has a static IP address of 192 168 1 51 Subnet Mask 255 255 255 0 Default Gatewa...

Страница 14: ...Configure four primary sub menus card proper operation Configuration Network Configuration SNMP Configuration Email and Configuration System Time 1 Configuration Network Enter a unique IP address to identify the SNMP card on your network ...

Страница 15: ...m Name field using the SNMP sub menu The System Name appears in the subject line of the event notifications emails The System Location only appears in the body of the email 3 Configuration Email Email Settings Enter the information for the sending Email Server and sender s account information ...

Страница 16: ...ne email account and an email client program like Outlook offering a central point for management updating and security Using an individual s email address could be a problem later if the person s responsibilities change or multiple technicians enter their email address Emailing of UPS Events Enter the email addresses of the people needing to receive UPS event notifications The Select button allow...

Страница 17: ...17 Event Notifications CY54 03 Model Event Notifications CY54 04 Model ...

Страница 18: ...Report Enter the email addresses of the people needing to receive a daily copy of the event and data logs as a CSV file The data and event logs are also available for download using the card s UI 4 Configuration System Time ...

Страница 19: ...ress Format AT T number txt att net SMS number mms att net MMS Boost Mobile number smsmyboostmobile com SMS number myboostmobile com MMS Cricket number sms cricketwireless net SMS number mms cricketwireless net MMS Sprint number messaging sprintpcs com SMS number pm sprint com MMS T Mobile number tmomail net SMS and MMS US Cellular number email uscc net SMS number mms uscc net MMS Verizon number v...

Страница 20: ...card is configured faster and easier Remember to change the new card s IP address and System Name Save Restore Settings Save Current Configuration Click on Save to save the configuration to your PC The text file has a default format of YYYY_MMDD_TIME cfg Restore the previous configuration Use this function to restore the cfg configuration file Click Browse to locate the file you want to restore an...

Страница 21: ...idual IP addresses and upgrade firmware Available at https marathon power com s Netility rar The Netility main page has a function section and an Online NetAgent card List 2 Function 2 1 Launch Web User Interface 2 2 Network Settings 2 3 Firmware Upgrade 2 4 About 2 5 Refresh List 1 2 Individual card Info 1 1 Online NetAgent card List 1 Online NetAgent 9 card ...

Страница 22: ...22 1 Click on a specific card 2 Click on Network Settings Select to assign IP by DHCP Columns requires to be entered for Static IP address ...

Страница 23: ...23 Default port for each protocol Enter password Once password is enabled and configured it is required to enter the correct password when change any setting or firmware upgrade ...

Страница 24: ...ersion and MAC address at the bottom of the page Double clicking on a card takes you to the card s webpage or select a card from the list and click on Launch Web User Interface to log in to the card s webpage Network Settings When selecting DHCP or BOOTP a network router assigns the IP address and other network parameters The card offers 4 network protocols HTTP HTTPS TELNET SSH If you need to cha...

Страница 25: ...ashes DO NOT remove the card from the UPS The updating process takes approximately 5 minutes 5 After Netility displays that the card was successfully updated click on Cancel to close the window If a failure occurs during firmware upgrading please try to upgrade the card again If the 2nd attempt fails please contact Marathon Power at support marathon power com Refresh List The list on Netility woul...

Страница 26: ...face Information System Status Basic Information Current Status Remote Control Meter Chart Configuration UPS Configuration UPS On Off Schedule Network SNMP Email SMS Web Telnet System Time Language Log Information Event Log Data Log Battery Test Log Help Search The card Serial Port Debug Help About ...

Страница 27: ...tion and configuration Basic Information Shows the UPS s information Battery Information Rating Information Current Status Input Status Output Status Battery Status When an abnormal condition occurs it appears in red Event Log and Event Timer Only Available on the CY54 04 Model Summary Only Available on the CY54 04 Model This shows a summary of the current UPS status Contact Status Only Available ...

Страница 28: ...n be sent to a CY54 03 compatible UPS Dry Contact Status and Configuration Only Available on the CY54 04 Model This is where each of the dry contact relays are configurated Each dry contact can be configured to change state for an On Battery a Low Battery a Timer an Alarm Condition a Fault Condition or can be disabled Meter Chart Only Available on the CY54 03 Model The Meter Chart section allows t...

Страница 29: ...ing Battery Exhausted Charge Voltage V 1 667 is the default setting Do not change this setting Date of Last Battery replacement mm dd yyyy Enter the Month Day Year Do Not change any of these settings The standard MegaTec firmware was customized to work with our UPSs firmware without changing these settings Changing these settings will not have any effect Except for entering the Date of Last Batter...

Страница 30: ...en the SNMP card retrieves data from the UPS Critical Battery Capacity Only Available on the CY54 03 Model When UPS battery capacity reaches the capacity configured the card sends a warning notification UPS On Off Schedule Only Available on the CY54 03 Model We do not recommend scheduling the UPS to turn Off UPS Action UPS Shutdown When the selected Action Event occurs the UPS shuts down The four ...

Страница 31: ...n If the card and UPS lose communication the card sends a warning notification at this configured time Critical load When loading reaches the configured the card sends a warning notification UPS Temperature C When the UPS temperature reaches the degree configured the card sends a warning notification ...

Страница 32: ... measuring the Battery Low Voltage AC Power Failed DC voltage 2 Do not copy the settings from one site to another The number of times the batteries were cycled used battery age and different loads affect each site s settings 3 Actual battery capacity may differ from the estimated battery capacity 4 It is vital to run additional backup time tests to correlate battery capacities to backup times Batt...

Страница 33: ... measured right at low battery shutdown You must record the minimum DC voltage before the battery voltage bounces back This bounceback is why you need a multimeter that retains a minimum DC voltage value Battery Low Voltage AC Power Normal is a couple of minutes after bounceback when the battery voltage without AC power stabilizes The UPS measures this voltage level when AC power returns and start...

Страница 34: ...ng Temperature Compensation Battery Voltage Low Warning External Fan On Off by Temperature Battery Test Options Inverter On Off Load Output ONLY This command turns off the output of the UPS only when the UPS is in battery mode It turns off the output ONLY NOT THE UPS Reset the Event Timer Counters Resets the UPS log timers and counters Change Password ...

Страница 35: ...rtations Our Line Interactive UPSs have a transformer with a second tap off the primary winding When Buck or boost is enabled the transformer automatically switches the secondary tap to buck or boost the output voltage by 10 Buck and boost are ideal when the AC line voltage is consistently higher or lower than nominal The transformer can buck lower or boost raise the output AC voltage without the ...

Страница 36: ...tery Mode Slow Detect Buck High When the input voltage exceeds this level TRTC SERIES UPS transfers to Buck Mode when enabled this reduces the output Slow Detect Buck Low When input voltage returns below this level TRTC SERIES UPS releases the Buck Mode when enabled and transfers back to Line Mode Slow Detect Boost High When input voltage returns above this level TRTC SERIES UPS releases the Boost...

Страница 37: ...96 120 96 120 102 105 Low Limit 90 120 90 120 90 100 Rebooting the UPS TRTC Series UPSs Using the SNMP CY54 04 SNMP Card go to Configuration Maintenance Battery Test Options 1 Start a Battery Test 2 While the Battery Test is running Use the Inverter On Off control below the Battery Test control to turn off the Inverter The output of the UPS turns OFF for 30 seconds The same procedure above can be ...

Страница 38: ...ure that the account and password are registered with the DDNS service provider Service Provider Select Dynamic DNS providers from a list Domain Name The Domain Name that you have created from the above selected DDNS provider Login Name Login Account name you created with the selected DDNS provider Login Password Enter the password you have assigned to your DDNS account Use an external STUN server...

Страница 39: ...side At the bottom of the page is Restart This reboots the SNMP card ONLY Not the UPS Auto Restart System for Every 0 is disabled The card to restart automatically at a preset hour or minute Manual Restart System After 30 seconds Once click on Apply The card restarts after 30 seconds ...

Страница 40: ...mmand Default is 161 TRAP Receive Port Default is 162 SNMPv3 Engine ID When using SNMPv3 the card requires you to have its Engine ID for identification which generates an authentication and encryption key SNMPv3 Engine ID Format Type The format type can be selected from the drop down list options MAC Address IPv4 IPv6 Manual options Clicking on Apply reboots the card Access Control Manager s IP Ad...

Страница 41: ... IP Addresses Accept Select the TRAP type from the drop down list When SNMPv3 TRAP or SNMPv3 Inform is selected username password and authentication information are required Community TRAP receiver and the card must have the same community Default is public MIB Type PPC MIB is the default RFC1628 MIB NOT recommended MIB files are available by contacting Marathon Power at support marathon power com...

Страница 42: ...evices connected to the same UPS if needed Email Email Settings Enter the information for the sending Email Server and sender s account information You must enter a Sender s email address to send email notifications We recommend using a unique email address account only for UPS event emailing instead of a person s email address This allows all the UPS emailing to be managed from one email account ...

Страница 43: ...43 Emailing of Power and UPS Events Enter the email addresses of the people needing to receive UPS event notifications Select The Select button allows you to select specific notifications to that person ...

Страница 44: ...44 Event Notifications CY54 03 Model Event Notifications CY54 04 Model ...

Страница 45: ...ail addresses of the people needing to receive a daily copy of the day s event and data logs as a CSV file The data and event logs are also available for download using the card s UI We recommend using 23 58 as the time to send a daily report ...

Страница 46: ... Address Format AT T number txt att net SMS number mms att net MMS Boost Mobile number smsmyboostmobile com SMS number myboostmobile com MMS Cricket number sms cricketwireless net SMS number mms cricketwireless net MMS Sprint number messaging sprintpcs com SMS number pm sprint com MMS T Mobile number tmomail net SMS and MMS US Cellular number email uscc net SMS number mms uscc net MMS Verizon numb...

Страница 47: ...ort Enter the SMS Server s port number for sending SMS Port 80 is the default Account Name Enter SMS Server s account name if required Password Enter SMS Server s password if required Sending test SMS Enter a mobile number when the configuration is finished to test the SMS Server configuration Mobile for Event Log To set the recipient s mobile number for SMS notification when an event occurs A tot...

Страница 48: ...or with a username and password One line User must have Read Write permission IP Filter Only allows a specific IP address to log in to the card means any IP address Auto Logoff after Idle for xx minute s 0 is disabled The user is logged off automatically once the preset time is reached SSL Information The card supports HTTPS protocol and various SSL encryptions for network connections The user may...

Страница 49: ...t if to enable RADIUS RADIUS Server Address To enter the IP address of the RADIUS Server Authentication Port RADIUS port number Default is 812 Shared Key Enter the Shared Key between RADIUS Server and client Connection Timeout Set the number of seconds to suspend the login time after the login Connection Retry Sets the number of connections to the RADIUS server again Please contact Marathon Power ...

Страница 50: ...elected from the drop down list or by adding it manually Recommended time windows com or time nist gov Time Zone Relative to GMT Use the drop down list to select its GMT zone Using Daylight Saving Time Select whether to use the daylight saving time system to adjust the clock for 1 hour Rebooting the Card Go to Configuration System Time Restart Reboots the SNMP card ONLY not the UPS Auto Restart Sy...

Страница 51: ...etects the OS language of the PC and shows the same language on its web pages Users may also choose the language per preference Note Users have to enable cookies before they use this function Email Preference Select a language preference for the email and SMS messages ...

Страница 52: ...y Loading Capacity Log capacity is 5000 logs When the limit is reached the card overwrites the oldest log Data Logs are saved in the CSV format by clicking on Save Data Log Battery Test Log Only Available on the CY54 03 Model The Battery Test Log is a log of each time the UPS remote control Self Test under System Information was run UPS Event Log Only Available on the CY54 04 Model The UPS Event L...

Страница 53: ...ions instead of adjustment and settings options illustrating each feature option that the NetAgent card offers An important note is that this could be an exact copy of your actual card Keep this in mind or you may confuse the Help Tab with your actual card Save Restore Settings Save Current Configuration Click on Save to save the configuration to your PC The text file has a default format of YYYY_...

Страница 54: ...tus System Information Updating the CY54 04 Card s Firmware Important Note If the firmware installed on your CY54 04 card is older than 3 8 CY504 PB 10 please contact Marathon Power at support marathon power com for the latest firmware Warning It is EXTREMELY IMPORTANT that you do not use the Update Now if the user netagent9 is visible WRONG SETTINGS Using User netagent9 will download MegaTec s st...

Страница 55: ...55 To see what firmware version is installed on your card go to Information System Status System Information About Shows the card s hardware version firmware and serial number ...

Страница 56: ...own password 2 Open a web browser and type http xxx xxx xxx xxx password cgi xxx xxx xxx xxx is the IP address of the card and click Enter For the ID enter admin For the password Enter the password located on the label under the SNMP card 3 Press continue and clear The username and password have been cleared removed and you can log into the card ...

Страница 57: ...rathon Power Inc MP_SNMP Net Agent User Manual_Apr_2022 Marathon Power Inc 2022 2538 E 54th Street Huntington Park CA 90255 Office 310 689 2328 Fax 310 689 2329 support marathon power com www marathon power com ...

Отзывы: