3. Route the communication cable to the PLC/host. Refer to the “OIT Cable

Routing” section for more information.

4. Connect the other end of the cable to the PLC/host and tighten the cable screws.

5. Connect the green shield wire from the cable to earth ground (chassis

ground) on the PLC. If this wire is not present, the ground connection was

made inside the connector.

1010-0105, REV 03

14

OIT3160B/4160B

PIN#

FUNCTION

1

TXD+

2

TXD-

3

CTS

4

RETURN

5

TXD

6

RXD

7

RXD-

8

RXD+

Figure 6 Port 1 Pin Outs

2. Control Panel Design Guidelines

The following guidelines are intended to illustrate proper installation of the OIT to

help minimize electrical noise, which may hamper normal operation.

It is the

responsibility of the customer to ensure that all wiring and other components

used in the control system meet Class I, Division 2 requirements. This

installation manual is intended only as a general guide to be used in conjunction

with the appropriate Class I, Division 2 installation and wiring requirements.

The customer is ultimately responsible for proper installation.

Pay careful attention to the placement of system components and associated cable

routing. These items can significantly enhance the performance and integrity of

your control application.

2.1. Control Panel Grounding

• The control panel should be connected to a good, high-integrity earth ground

both for safety considerations and shielding purposes. This must be a reliable

earth ground with a low-resistance path. The ideal earth ground would be a

copper grounding rod located close to the OIT and the control panel.

• Hinged doors on control panels do not provide a long term electrical connection

to the rest of the enclosure. Corrosion develops over time and prevents good

electrical contact. For this reason, a separate wire braid should be installed from

the hinged control panel to the rest of the enclosure.

1010-0105, REV 03

INSTALLATION MANUAL

7

Figure 1 Control Panel Example

Содержание OIT 3160B

Страница 1: ...45 3429 E mail maple maple systems com URL www maple systems com 8 7 4 5 Alarm Ack 9 CLEAR ENTER 6 Help 1 2 Page Down 3 0 F3 F6 F2 F5 Del F1 F4 Toggle 8 7 4 5 Alarm Ack 9 CLEAR ENTER 6 Help 1 2 Page D...

Страница 2: ...products and documentation at any time without notice IF SERVICE IS REQUIRED Package the unit in its original packaging container or if unavailable any suitable rigid container If a substitute contain...

Страница 3: ...r operational software installed therefore The OIT will NOT operate until it has been configured using OITware 200 or STEPware 100 When power is first applied the OIT s display will indicate that it n...

Страница 4: ...carefully if any shipping damage is evident notify the carrier immediately You are responsible for claimnegotiations with the carrier Save the shipping container and packing material in case the equip...

Страница 5: ...x 7 dot matrix with cursor Display Character Size 2 lines of 20 characters 0 19 inches 4 8 mm high Display Viewing Angle Approximately 90 degrees Keypad Key Type Membrane switch with custom legending...

Страница 6: ...bed in the National Electrical Code ANSI NFPA 70 WARNING Use only with Class 2 power source limited to 30 VDC open circuit and 8A short circuit 1010 0105 REV 03 6 OIT3160B 4160B 4 OIT Configuration Wi...

Страница 7: ...ly as a general guide to be used in conjunction with the appropriate Class I Division 2 installation and wiring requirements The customer is ultimately responsible for proper installation Pay careful...

Страница 8: ...PLC host control wires Never bundle the OIT cables together with 120 VAC power wires or with relay wiring Try to keep at least 8 inches 20 cm of separation between the OIT cables and other power wirin...

Страница 9: ...le c Strip the insulation from the two insulated wires For the OIT end this is 0 27 inch 7 mm 1010 0105 REV 03 12 OIT3160B 4160B Figure 4 OIT3160 4160 Power Supply Connection Keep the lengths of the O...

Страница 10: ...hat prevent the gasket from sealing properly The diagram in Appendix D shows the dimensions of the panel cutout required for proper installation This panel cutout illustration is shown actual size and...

Отзывы: