OPERATION SUMMARY - Section 3
3-40 MTS-3000 SERIES OPERATION AND REFERENCE MANUAL
#
0$17$
#
7(67
#
6<67(06
###########################################
CU M004 01A
4.
To test other fault elements of the relay (e.g.
Φ
-G or 3
Φ)
, select the new fault type as described above
in Step 2 of the previous section.
3.3.15.3 MTA TEST.
1.
If you haven’t done so, perform the preliminary steps described in Preparation above, and complete the
Reach Test described in the previous section to find the reach at the theoretical Maximum Torque
Angle. Decrease voltage or increase current slightly to move the impedance locus within the operate
area of the relay.
2.
Enable the voltage-to-current phase angle adjustment by pressing F3 on the Control Module. Energize
the outputs with the Fault button or External Start signal. Increase the phase angle by turning the
MODIFY knob clockwise until the relay drops out. Record this value.
3.
Decrease the phase angle by turning the MODIFY knob counterclockwise until the relay first picks up,
then drops out again. Record the second value.
4.
The MTA is the average of the two recorded values.
5.
Release the FAULT button or the external start input signal.
3.3.15.4 OPERATE TIME TEST.
1.
If you haven’t done so, perform the preliminary steps described in Preparation above, and complete the
Reach Test described in the previous section to find the reach at the theoretical Maximum Torque
Angle. Set the phase angle to the MTA.
2.
Decrease voltage or increase current slightly to move the impedance setting to the desired percent of
reach for the test.
3.
Release the FAULT button or External Start signal to de-energize the AC outputs. Now press the
FAULT button momentarily and release. The AC outputs will seal in until the relay operates, freezing
the timer reading on the Control Module, tripping off the AC outputs, and bringing on the TRIP LED.
4.
Press RESET to clear the timer and restore prefault conditions.
Содержание MTS-3000 Series
Страница 12: ...TABLE OF CONTENTS xii MTS 3000 SERIES OPERATION AND REFERENCE MANUAL 0 17 7 67 6 67 06 CU M004 01A ...
Страница 64: ...OPERATION SUMMARY Section 3 3 44 MTS 3000 SERIES OPERATION AND REFERENCE MANUAL 0 17 7 67 6 67 06 CU M004 01A ...
Страница 114: ...QUICKTEST Section 6 6 20 MTS 1700 SERIES OPERATION AND REFERENCE MANUAL 0 17 7 67 6 67 06 CU M004 01A ...
Страница 132: ...RS 232C INTERFACE Section 7 7 18 MTS 3000 SERIES OPERATION AND REFERENCE MANUAL 0 17 7 67 6 67 06 CU M004 01A ...
Страница 152: ...GLOSSARY D 4 MTS 3000 SERIES OPERATION AND REFERENCE MANUAL 0 17 7 67 6 67 06 CU M004 01A ...
Страница 156: ...INDEX E 4 MTS 3000SERIESOPERATIONANDREFERENCE MANUAL 0 17 7 67 6 67 06 CU M004 01A ...