Manson Engineering Industrial SBC-7100 Series Скачать руководство пользователя страница 12

Activate the feature

Please follow the steps below:

                                                                               
                                                                     

                          
                                                                           

Connection

Use the

 

RJ-45 connector (8-pin) to control ON/OFF of the LED and Equipments.

The pins configuration and connection are as follow:

Pin 1 & 2

On/Off Control Signal synchronized with Night-light Mode

Pin 7 & 4

High/Low control signal (12V, 0V) up to 0.1A, synchronized with Night Light mode

Pin 6 & 4

Shows the battery status Red LED (See Section 3.2)

Pin 8 & 4

Shows the battery status Green LED (See Section 3.2)

Table 7 

Pins configuration

 

Note: Pin 3 and 5 are not used in Remote signal Terminal.

 

Rev.6  02/2012

7673-7112-0566

Figure 8

1.

Open the case of the controller, there should
be   a   small   control   board   near   the   Remote
Signal Terminal as shown in figure 6.

2.

On the small control board, there is a sky blue
color dip switch. Turn the dip switch 1 and 2
to 

ON

 position as shown in figure 7.

Figure 10

Figure. 11   Connection diagram of RJ-45 to Equipments.

Figure 9

END

Содержание SBC-7100 Series

Страница 1: ...PV Charge Controller Settings 4 3 4 2 Select the Auto Manual Equalization charging and Night Light Mode 6 4 PV Charge Control Mode 6 4 1 3 Stage Charge Control 6 4 2 Equalization Charging Mode Automa...

Страница 2: ...plastic tape or vinyl dip coating material Specifications SBC 7100 Series Models 7108 7112 7120 Battery voltage 12V Maximum PV panel open circuit voltage 26V Continuous load charge current 8A 12A 20A...

Страница 3: ...Adjustable Low Voltage Disconnect and Low Voltage Reconnect Build In Microprocessor for PV charge control to maximize the charging efficiency Overcharge and Over discharge Protection Over Temperature...

Страница 4: ...rge Controller should be installed in a dry sheltered location away from sources of high temperature and moisture 3 2 LED Indicator Red Flashing Battery Voltage is lower than 12 6V Constant Red Batter...

Страница 5: ...the total Ampere Hour input to the system in current day L1D PV_AH Shows the total Ampere Hour input to the system a day before L2D PV_AH Shows the total Ampere Hour input to the system 2 days before...

Страница 6: ...rer s specific recommended values How to adjust the Bulk Float Charge Voltage LVD LVR and Night Light Mode 1 First take out all the connections to the PV controller except those to battery 2 Push up t...

Страница 7: ...ation Eq charging is only for wet type Lead Acid Battery When Auto Equalization Charging is set at ON mode Equalization charge will occur for 2 hours once every thirty days Use the dip switch to selec...

Страница 8: ...olt age Setting for one full hour with various rapid On Off pulses PWM It then switches to Float Charge Mode c FLOAT CHARGE The controller will maintain the battery voltage at the float voltage settin...

Страница 9: ...ce and the controller will return to the charging mode before the Equalization charge 4 3 12V DC Load Terminal Control Mode The 12V DC load terminal is designed for low power DC load such as street li...

Страница 10: ...in Z hours before sunrise Dusk to Dawn Load is turned on all night Measure Night Length The load timer options that turn the load on again before sunrise require that the PV charge controller to measu...

Страница 11: ...rotection The operation temperature of the transistors of the PV Charge Controller is also continuously monitored If excessive temperature is detected the charge controller transistors will repeatedly...

Страница 12: ...the battery status Red LED See Section 3 2 Pin 8 4 Shows the battery status Green LED See Section 3 2 Table 7 Pins configuration Note Pin 3 and 5 are not used in Remote signal Terminal Rev 6 02 2012 7...

Отзывы: