8. Electrical Connections: Electronic Humidity Model (Diagram 3) 

For the fan to operate as a normal time delay unit with humidity over-ride i.e. when connected with a 
switched live coming from the light switch into the fan, the fan will operate when the light is switched on, 
and switch off after about 20 seconds to 20 minutes (timer is pre-set for the minimum). However should 
the humidity in the room reach about 75%, which will happen if the shower is run or the bath filled with 
hot water, the fan will switch on and keep running until the humidity has been reduced to a normal level, 
about 65%. Connect to electrical supply as shown in diagram 3. 

Neutral

 Switched Live

Spare

Permanent Live

PCB Board Cover

Motor Wire

Humidity operated time delay control

Diagram 3

Time delays & humidity 
over-risde operation 
Terminal 1 - 1 Neutral
Terminal 2 - 2 Switch live Supply
Terminal 3 - 3 Spare
Terminal 4 - 4 Permanent Supply 

077286

LP100, LP120, T. Max 40°C Rated 220-240V ~50Hz 20W 

q

 

IP24  

LP150, T. Max 40°C Rated 220-240V ~50Hz 25W 

q

 

IP24

CABLE ENTRY

FIXING HOLES

CABLE
GRIP

MOTOR WIRE

MIN

MAX

10

30

15

20

+

DETAILED VIEW

Only adjust with power switched off

TIMER MIINUTES

PCB BOARD

COVER

POWER

CABLE

ENTRY

1

3 AMP

DOUBLE POLE

FUSED SPUR

_
NEUTRAL

+

LIVE

PULLCORD

SWITCH / LIGHT SWITCH

MIN

MAX

10

30

15

20

+

        Switched Live

                  Permanent Live

                Neutral

1

FIXING HOLES

40

50

60

70

80

90

98

OFF -

+ MAX

Содержание LP 100

Страница 1: ...hould be arranged to slope slightly away from the fan Ducts passing through cold voids must be suitably insulated 4 Do not install the unit within a shower cubicle or anywhere else where there is a risk of being sprayed with water Please see our range of showerfans for these installations 5 If the fan is installed in a room containing a fuel burning appliance the installer must ensure that the air...

Страница 2: ...on as marked Allow an extra 230mm 9 protruding to facilitate connection SECURE CORD GRIP 9mm 6mm 9mm 9 m m 2 3 POWER SUPPLY PO W ER SU PP LY Terminal 1 live supply in Terminal 2 neutral supply in TRIM CABLE TERMINAL BLOCK POWER CABLE ENTRY MOTOR WIRE POWER CABLE COVER SCREW FIXING HOLES 3 AMP DOUBLE POLE FUSED SPUR _ NEUTRAL LIVE REMOTE PULLCORD SWITCH LIGHT SWITCH HOLES FIXING HOLES Fixing clip C...

Страница 3: ...e increased by firstly switching off the power to the fan Remove the cover and the timer cover as detailed in diagram 2A Insert a small screwdriver into the slot marked in Diagram 2A and turn clockwise to reduce the time and anti clockwise to increase the time Only adjust with power switched off the timer will run for is 30 seconds and the maximum is about 20 minutes NB Timer delay is adjustable a...

Страница 4: ...duced to a normal level about 65 Connect to electrical supply as shown in diagram 3 Neutral Switched Live Spare Permanent Live PCB Board Cover Motor Wire Humidity operated time delay control Diagram 3 Time delays humidity over risde operation Terminal 1 1 Neutral Terminal 2 2 Switch live Supply Terminal 3 3 Spare Terminal 4 4 Permanent Supply 077286 LP100 LP120 T Max 40 C Rated 220 240V 50Hz 20W q...

Отзывы: