background image

b. Randomly check concrete subfloor for porosity using the drop water test. Place a 1 inch diameter drop of water

directly onto the concrete subfloor. If the water droplet does not dissipate within 60 to 90 seconds the subfloor

is considered non-porous. If the substrate is too porous apply Mannington Premium Universal Primer to render

the surface suitable for adhesive and floor covering.

c.  Concrete subfloors must have a minimum compressive strength of 3000 psi.

d. Concrete subfloors shall not consist of lightweight concrete or gypsum with less than 105 lbs. /cubic foot density.

e.  Moisture Testing: Perform either the preferred In-situ Relative Humidity (RH) Test (ASTM F2170) or the acceptable

Moisture Vapor Emission Rate (MVER) Test (ASTM F1869). Acceptable moisture limits must not exceed 3lbs per

1000 square feet per 24 hours 1869 or 75% per 2170.

f. Alkalinity: Must test surface alkalinity (ASTM F710). A 7.0 to 9.0 pH is acceptable. Reduce higher pH by applying

Mannington 

Premium 

Universal 

Primer.

6.  Wood Subfloors and underlayment panels shall have the moisture content tested using a suitable wood pin meter.

Readings between the wood subfloor and underlayment pan should be within 3% and have a maximum moisture

content of 14% or less. Effective moisture control in basements and crawlspaces is essential for achieving a successful

long term installation.

MOISTURE SUPPRESSANT SYSTEM 

Concrete subfloors that exceed adhesive specifications will require a Moisture Suppressant System. Due to complexities 

associated with moisture vapor transmission, emissions and movement of soluble salts (alkalinity) in concrete subfloors, we do 

not offer, recommend or warranty a specific solution for excess moisture in concrete slabs. However, there are many 

companies that offer solutions with warranties for excess moisture in concrete slabs. 

Mannington Commercial suggests that you reference the current ASTM F710, “Standard Practice for Preparing Concrete 

Floors to Receive Resilient Flooring” and contact one or more of the following or other moisture suppressant system suppliers 

for assistance: 

Ardex (724) 203-5000 www.ardex.com

Koester American Corp. (757) 425-1206 www.koesterusa.com 

Mapei (800) 426-2734 www.mapei.com 

Uzin Ltd. (800) 505-4810 www.ufloorsystems.com

SUBFLOOR PREPARATION 

Concrete

Careful subfloor preparation is vital for an excellent floor appearance and good sheet adhesion. The subfloor must be smooth, 

firm, flat, clean, dry, and free from defects and fit for purpose. A suitable smoothing compound should be used to ensure that 

no irregularities show through to the surface of the finished floor. In all cases, the subfloor must meet the moisture and pH 

requirements before installation. 

Below and On-grade concrete subfloors must have a suitable vapor retarder properly installed beneath the slab. Crawlspaces 

and basements directly beneath the new floor installation should be maintained with a relative hu/- 10% of the room 

relative humidity where the flooring is installed. This can be accomplished by proper ventilation and air circulation or using a 

dehumidifier. Always follow other manufacturers’ written recommendations for the use and installation of their proprietary 

surface preparation materials. 

1.  Record site conditions, test results and corrective action(s). Mannington Commercial requires written documentation of

site conditions, test results and corrective action(s) before processing claims.

2.  Subfloor must be clean (free of dirt, sealers, curing, hardening or parting compounds or any substance that may stain or

prevent adhesion), smooth, flat, sound, fit for purpose, free of movement, excessive moisture and high alkalinity.

3.  Slick surfaces such as power troweled concrete shall be profiled to allow for a mechanical bond between the adhesive

and 

subfloor.

4.  Remove existing resilient floor covering, 100% traces of old adhesives, paint or other contaminants by scraping,

sanding, grinding, shot blasting or scarifying the substrate. The use of adhesive removers or solvents in the abatement

or removal of existing or old adhesives is prohibited and may void any warranty.

WARNING: ASBESTOS & SILICA

 

- Refer to the current Resilient Floor Covering Institute (RFCI) document “Recommended 

Work Practices for Removal of Existing Resilient Floor Coverings” for guidance. 

Choices that Work.

Questions about warranties? call 800 241 2262 or visit www.manningtoncommercial.com 

July, 2015 

Insight

®

 Plus GB

Installation Guidelines

Insight

®

 Plus GB Instal

lat

ion Guidel

ines

Содержание Insight Plus GB

Страница 1: ...materials for subfloor preparation MATERIAL RECEIVING HANDLING STORAGE 1 Always store Insight Plus GB tightly rolled face out on a sturdy cardboard core designed for that purpose Store the roll horizo...

Страница 2: ...can Corp 757 425 1206 www koesterusa com Mapei 800 426 2734 www mapei com Uzin Ltd 800 505 4810 www ufloorsystems com SUBFLOOR PREPARATION Concrete Careful subfloor preparation is vital for an excelle...

Страница 3: ...ess Have a written warranty for suitability and performance from the panel manufacturer or have a history of proven performance e Any unevenness at the joints between panels must be sanded to a level...

Страница 4: ...placing the Insight Plus GB into the wet tacky MT 711 adhesive with a 1 16 x1 32 x1 32 notched trowel the substrate must be smooth and have sufficient porosity to receive the adhesive For wood substr...

Страница 5: ...o the adhesive to eliminate trapping air Do not drop or flop the material into the adhesive Using a 50 lb or heavier three section floor roller roll the material in both directions starting in the mid...

Страница 6: ...n determining the direction of sheet or fill piece if needed REVERSE METHOD Reverse Sheets for Seaming means turning the second sheet 180 to the first sheet To determine the amount of additional mater...

Страница 7: ...ong the length of the seam You must apply seam sealer into the seam cut and leave a bead of sealer approximately 1 8 wide centered on the seam Remember it is crucial that the seam sealer be applied to...

Страница 8: ...deep If the Insight Plus GB was installed FULLY ADHERED apply a thin layer of MT 711 to the back of the repair piece and place into position Roll with a hand roller Apply MLG 33 seam sealer Protect f...

Отзывы: