TRI-LOCK OPERATION AND MAINTENANCE

Handling, Storage

 

And Installation

HANDLING AND STORAGE OF FILTER 
ELEMENTS

Particulate filters include a wide range of filter 
types, sizes and performance capabilities. These 
filters are designed to remove airborne 
particulates from an air stream. Filters can range 
from 30%-efficient (MERV 7) prefilters up to 
99.97% @ 0.3μm-efficient HEPA (high efficiency 
particulate air) filters. In general, all particulate air 
filters are fragile and should be handled with care. 
The following precautions should be observed 
upon storing filters:

  Keep in a clean, low humidity, air-controlled 

environment.

  Filter should remain in its original shipping 

container with the correct orientation until it is 
installed.

  The temperature in the storage area should not 

be lower than 0° F or higher than 100° F.

  Stacking of filters is not recommended.

  Movement of filters should be restricted to 

reduce the chance of damage to the media.

  Any additional filter manufacturer’s instructions 

and warnings should also be followed.

INSTALLATION OF NEW HOUSINGS

1. 

Position the housing adjacent to the ductwork. 

Housing should be welded, bolted or gasketed 
permanently to the ductwork.

2. 

Housing should be securely mounted to either 

a base or other permanent edifice.

3. 

Unit should be orientated so the access door(s) 

can be easily removed and replaced.

4. 

Following installation, ductwork and housing 

should be cleaned to eliminate any and all 
contaminants, as well as any other items 
that may have been stored in the unit during 
shipping.

5. 

Install filter(s) and tighten the mechanism 

(gasket seal) or engage the arm (gel seal).

6. 

Perform designated leak test/DOP test 

(designated by either the chief safety officer 
or engineer) to ensure that the unit is working 
properly and not leaking.

Содержание TRIDIM Tri-Lock GS

Страница 1: ...Tri Lock GS FS Operation Maintenance Manual...

Страница 2: ...TION AND MAINTENANCE Tri Lock Operation Maintenance CONTENTS Introduction 3 Application 3 Performance 4 Handling and Storage of Filter Elements 6 Installation of New Housings 6 Start Up Procedures 7 A...

Страница 3: ...nnel and no extrusion Hat sections are located on the top bottom and back of the unit for structural support Each housing is custom manufactured to meet specific end user requirements The unit is cons...

Страница 4: ...echanism guides and secures the filter into the knife edge penetrating the gel and forming a positive seal on the filter face DESCRIPTION OF FLUID SEAL FILTER LOCKING SYSTEM The fluid seal Tri Lock FS...

Страница 5: ...or each filter element apply consistent pressure to maintain the filter seal The applied force has a minimum clamping load of 1 400 pounds per perimeter of the filter The gasket on the filter is compr...

Страница 6: ...r than 0 F or higher than 100 F Stacking of filters is not recommended Movement of filters should be restricted to reduce the chance of damage to the media Any additional filter manufacturer s instruc...

Страница 7: ...e Option lift the door off the hinge and place in a safe location 4 Unseal the filter Pull the arm all the way outward to the open position The mechanism will pull the filters from the gel track via e...

Страница 8: ...eal Method 1 Using the ratchet with a socket remove the two hex nuts and washers for both the top and bottom locking trays 2 Then switch to a socket and remove the hex nut and washers from the linkage...

Отзывы: