166
Part Number 80-1479-3 7/10
FAN CYCLE CONTROL VS. HEAD PRESSURE
CONTROL VALVE
A fan cycle control cannot be used in place of a head
pressure control valve. The fan cycle control is not
capable of bypassing the condenser coil and keeping
the liquid line temperature and pressure up.
This is very apparent when it rains or the outside
temperature drops. When it rains or the outside
temperature drops, the fan begins to cycle on and off.
At first, everything appears normal. But, as it continues
raining or getting colder, the fan cycle control can only
turn the fan off. All the refrigerant must continue to flow
through the condenser coil, being cooled by the rain or
low outside temperature.
This causes excessive sub-cooling of the refrigerant.
As a result, the liquid line temperature and pressure
are not maintained for proper operation.
Downloaded from
www.Manualslib.com
manuals search engine
Содержание SD0302A
Страница 2: ...Downloaded from www Manualslib com manuals search engine ...
Страница 36: ...36 Part Number 80 1479 3 7 10 A B C D E Downloaded from www Manualslib com manuals search engine ...
Страница 45: ...Part Number 80 1479 3 7 10 45 A B C D E F G Downloaded from www Manualslib com manuals search engine ...
Страница 48: ...48 Part Number 80 1479 3 7 10 A A B C D E F G H I Downloaded from www Manualslib com manuals search engine ...
Страница 184: ...184 Part Number 80 1479 3 7 10 SV1406 USING PINCH OFF TOOL Downloaded from www Manualslib com manuals search engine ...
Страница 298: ...298 Part Number 80 1479 3 7 10 Downloaded from www Manualslib com manuals search engine ...
Страница 299: ...Downloaded from www Manualslib com manuals search engine ...