SYMPTOM #3 - TRADITIONAL REMOTES ONLY
Refer to Symptom
#2 - Freeze Cycle
Analysis Chart
Traditional Remote Ice Machine - Long Harvest/Low Production/Intermittent Safety Limit 2
Fails at night or in low
ambient - Operates
normally above 70F/21C
YES
YES
YES
NO
Liquid Line Temperature Cool
NO
Liquid Line
Temperature Hot
Liquid Line
Temperature Warm
(body temperature)
Wet condenser
with water during
freeze cycle
Replace Headmaster
System low on refrigerant
Normal ice fill, long harvest cycle,
possible SL #2, back of cubes are
not melted at the end of harvest cycle
Discharge line temperature
is normal at the end of the
freeze cycle?
All S Model Remotes = >150F/65C