Electrical System
Section 6
6-14
Part Number 80-1558-3
COMPRESSOR ELECTRICAL DIAGNOSTICS
The compressor will not start or will trip repeatedly on
overload.
Check Resistance (Ohm) Values
NOTE: Compressor windings can have very low ohm
values. Use a properly calibrated meter.
Perform the resistance test after the compressor cools.
The compressor dome should be cool enough to touch
(below 120°F/49°C) to assure that the overload is closed
and the resistance readings will be accurate.
SINGLE PHASE COMPRESSORS
1. Disconnect power from the cuber and remove the
wires from the compressor terminals.
2. The resistance values between C and S and
between C and R, when added together, should
equal the resistance value between S and R.
3. If the overload is open, there will be a resistance
reading between S and R, and open readings
between C and S and between C and R. Allow the
compressor to cool, then check the readings again.
THREE PHASE COMPRESSORS
1. Disconnect power from the cuber and remove the
wires from the compressor terminals.
2. The resistance values between L1 and L2, between
L2 and L3, and between L3 and L1 should all be
equal.
3. If the overload is open, there will be open readings
between L1 and L2, between L2 and L3, and
between L3 and L1. Allow the compressor to cool,
then check the readings again.
Check Motor Windings to Ground
Check continuity between all three terminals and the
compressor shell or copper refrigeration line. Scrape
metal surface to get good contact. If continuity is
present, the compressor windings are grounded and the
compressor should be replaced.
Determine if the Compressor is Seized
Check the amp draw while the compressor is trying to
start.
COMPRESSOR DRAWING LOCKED ROTOR
The two likely causes of this are:
•
Defective starting component
•
Mechanically seized compressor
To determine which you have:
1. Install high and low side gauges.
2. Try to start the compressor.
3. Watch the pressures closely.
A. If the pressures do not move, the compressor is
seized. Replace the compressor.
B. If the pressures move, the compressor is turning
slowly and is not seized. Check the capacitors
and start relay.
COMPRESSOR DRAWING HIGH AMPS
The continuous amperage draw on start-up should not
be near the maximum fuse size indicated on the serial
tag.
Diagnosing Capacitors
•
If the compressor attempts to start, or hums and trips
the overload protector, check the starting
components before replacing the compressor.
•
Visual evidence of capacitor failure can include a
bulged terminal end or a ruptured membrane. Do not
assume a capacitor is good if no visual evidence is
present.
•
A good test is to install a known good substitute
capacitor.
•
Use a capacitor tester when checking a suspect
capacitor. Clip the bleed resistor off the capacitor
terminals before testing.
Содержание S0850M
Страница 24: ...Ice Machine Operation Section 3 3 6 Part Number 80 1558 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 66: ...Electrical System Section 6 6 28 Part Number 80 1558 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 92: ... Refrigeration System Section 7 7 26 Part Number 80 1558 3 Figure 7 10 Using Pinch Off Tool SV1406 ...
Страница 97: ...Section 7 Refrigeration System Part Number 80 1558 3 7 31 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 98: ... Refrigeration System Section 7 7 32 Part Number 80 1558 3 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 99: ......