Section 2
Installation Instructions
Part Number 000001759
2-9
Remote Condenser/Line Set Installation
REMOTE ICE MACHINE REFRIGERANT CHARGE
Each remote ice machine ships from the factory with a
refrigerant charge appropriate for installation with line
sets of up to 30 m. .
Ice Machine
Remote Single
Circuit
Condenser
Line Set*
Q1060
Q1090
JC1096
RT-20-R404A
RT-35-R404A
RT-50-R404A
*Line Set
Discharge Line
Liquid Line
RT
12.7 mm
7.9 mm
Air Temperature Around the Condenser
Minimum
Maximum
-29°C
49°C
!
Warning
Potential Personal Injury Situation
The ice machine contains refrigerant charge. Installation of
the line sets must be performed by a properly trained and
certified refrigeration technician aware of the
dangers of
dealing with refrigerant
charged equipment.
Ice Machine
Nameplate Charge
(Charge Shipped in Ice Machine)
Refrigerant to be Added for
15 m - 30 m Line Sets
Maximum System Charge
(Never Exceed)
Q1090
Q1060
4.4 kg
None
4.4 kg