ELECTRIC SYSTEM
NBT30H-2 SERVICE MANUAL
3-22
03-20-2019 Control # 613-06
Base Side Pressure Sensor Calibration
Two calibration steps are shown one at a time on the Base
Side Pressure Sensor Calibration screen. Once a step has
been confirmed, the next step will be displayed. Follow
instructions on display to reprogram the rod side pressure
transducer.
-
Disconnect the electrical cable to rod side
transducer to temporarily remove it from the
CANBUS.
-
Press the checkmark to confirm.
-
Reconnect the electrical cable to the rod side
transducer.
-
Press the checkmark to confirm.
-
Save the new Node ID by cycling the power to the
base/piston side sensor using the ignition switch or
by manually disconnecting/reconnecting.
Pressing Button #2
will reset the calibrated values
for the base/piston side pressure sensor.
NOTE:
If Base side transducer is not connected, the icon
will have a red background.
Outrigger Length Calibration
Select the Outrigger length icon from the Outrigger length
Sensor Calibration menu screen (Figure 3-18) to start the
outrigger length sensor calibration.
Outrigger Length Sensor Calibration
Three calibration positions are shown on the Outrigger
Length Sensor Calibration screen one at a time starting with
the Fully Retract position. Once the outriggers have been
positioned and confirmed, the next calibration position will be
activated.
If an error message appears after a position has been
confirmed, the length sensors will need to be mechanically
adjusted.
NOTE:
If sensors are not within calibration range, the
outrigger icon will have a red background.
Pressing Button #2
will reset the calibrated values
for the outrigger length sensors.
Load Chart and RCL Download
RCL master module software updates, geometric charts,
load charts and calibration charts are down-loaded to the
RCL master module system using a laptop computer
connected to the crane control system through the
Diagnostic Connector (1, Figure 3-19). Contact Manitowoc
Crane Care for the required software and cables for the
crane interface.
CAUTION
For this procedure it is only necessary to disconnect the
pressure transducers electrically.If you do disconnect the
pressure transducers hydraulically, make sure there is no
h y d r a u l i c p r e s s u r e i n t h e h y d r a u l i c l i n e w h e n
disconnecting the pressure transducers. Pressurized
hydraulic fluid can cause personal injury.
8717-40
FIGURE 3-17
!
8717-41
FIGURE 3-18
8717-42
Содержание National Crane NBT30H-2
Страница 1: ...Service Manual National Crane NBT30H 2 ...
Страница 2: ......
Страница 40: ...1 30 03 20 2019 Control 613 06 INTRODUCTION NBT30H 2 SERVICE MANUAL ...
Страница 92: ...ELECTRIC SYSTEM NBT30H 2 SERVICE MANUAL 3 24 03 20 2019 Control 613 06 ...
Страница 110: ...BOOM MAINTENANCE NBT30H 2 SERVICE MANUAL 4 18 03 20 2019 Control 613 06 ...
Страница 132: ...SWING NBT30H 2 SERVICE MANUAL 6 14 03 20 2019 Control 613 06 ...
Страница 142: ...OUTRIGGERS NBT30H 2 SERVICE MANUAL 7 10 03 20 2019 Control 613 06 ...
Страница 158: ...LUBRICATION NBT30H 2 SERVICE MANUAL 8 16 03 20 2019 Control 613 06 ...
Страница 190: ...SCHEMATICS NBT30H 2 SERVICE MANUAL 10 2 ...
Страница 193: ......
Страница 194: ......