background image

 

 

    

 

 

 

 
 

 

 

 

 

K00364 Electronic Bin Thermostat 

 

 

 

            

        Installation Instructions 

 
This kit reduces overfill and condensation issues and can be used on any Manitowoc ice machine installed on an ice 
dispenser.  Order kit number K00336 for the following models IB0620, IB0820, IB1020, QF0400 and QF2300. 
 

Control Settings 

 

Flake/Nugget/Chiplet: 
The control  must be reset  from the factory setting.  
Refer to the jumper and control settings. 

 

 
Ice Cube Machines: 
The machines use the factory control settings. 
 
The controller has a one-minute time delay anytime 
power is interrupted and restored. 
 

Positioning the Touchpad Jumpers 

 
P5 Jumper 

The P5 jumper position determines if the touchpad is 
locked or unlocked. The control is factory locked; to 
unlock, move the jumper from one pin to two pins.

 

 

 

 
 

 

P4 Jumper 

The P4 jumper labeled Jump 1 is used to set the control 
for heating or cooling mode.  Jump 2 is used to 
establish set point at either cut-in or cut-out. 

 

 
 
 
 
 
 
 
 
 

   

Cubers 

        Flake/Nugget/Chiplet 

 

 

 

Setting Control Set point Value 

 
To view and adjust set point, follow these steps: 

 

A.

 

Press MENU until the display flashes SP.

 

B.

 

Press MENU again to display the existing set 
point value.

 

C.

 

Press  up or down (arrows) to change the set 
point value.

 

D.

 

Press MENU again to save the new value.  The 
display returns to the sensed temperature.

 

E.

 

If no setup entry is made for 30 seconds, the 
control reverts to the normal temperature 
display. 

 
IMPORTANT: 

If MENU is not pressed after changing the set point 
value, the control reverts to the previously 
programmed set point value. 
 
 
 
 
 
 
 
 
 

 

RED 
SENSOR 
LEAD 

BLACK 
SENSOR 
LEAD 

JUMPER 
LOCATIONS 

MATCH 
WIRING  
TO ICE 
MACHINE 
VOLTAGE 

BIN SWITCH OR 

TOGGLE SWITCH 

 

Содержание K00364

Страница 1: ...lock move the jumper from one pin to two pins P4 Jumper The P4 jumper labeled Jump 1 is used to set the control for heating or cooling mode Jump 2 is used to establish set point at either cut in or cut out Cubers Flake Nugget Chiplet Setting Control Set point Value To view and adjust set point follow these steps A Press MENU until the display flashes SP B Press MENU again to display the existing s...

Страница 2: ...2110 South 26th Street P O Box 1720 Manitowoc WI 54221 1720 USA 8016563 Telephone 920 682 0161 Fax Sales 920 683 7589 Service Parts 920 683 7585 Other 920 683 7879 Sheet 1 of 4 Web Site www manitowocice com Rev 03 14 06 ...

Страница 3: ...edures 1 Check for proper voltage to the control A Remove the cover by loosening the four cover screws B Use an AC voltmeter to check the voltage between the common and 120V or 240V terminals C The voltage must be between 102 and 132 volts for 120V applications 177 and 264 volts for 208 230V applications D If the voltage reading is not within the required range check the power source and input pow...

Страница 4: ...8016563 Sheet 2 of 4 Rev 03 14 06 ...

Страница 5: ...tubing IMPORTANT The thermostat must be wired to match the voltage of the ice machine The thermostat is pre wired for 115 volts Rewire thermostat if your ice machine is 240 volts 9 The control box line voltage wiring offers two options Connect thermostat L1 brown and L2 blue wires to contactor incoming line voltage side L1 and L2 OR Disconnect incoming power line wire nuts Remove quick connect fit...

Страница 6: ...8016563 Sheet 3 of 4 Rev 03 14 06 ...

Страница 7: ...Delay ASD 1 Temperature Offset OFS 0 Sensor Failure Operation SF 1 Cube 0 Flake Nugget Chiplet Keypad Locked Out Jumper Position Red Lead Sensor Probe Black Lead Sensor Probe Brown Lead Power Blue Lead Power Red 22AWG Lead Bin Switch or Toggle Switch White 22AWG Lead Bin Switch or Toggle Switch Route Sensor Wiring Here ...

Страница 8: ...8016563 Sheet 4 of 4 Rev 03 14 06 ...

Отзывы: