The dampers must be installed in compliance with all applicable safety standards and regulations.

 

Prior to commissioning the dampers and during subsequent serviceability checks, all versions,
including the operation of electrical components, must be inspected and functionally tested, and
the conductive connections of all moving and fixed parts (inside and outside the damper) must
be checked on the damper. After commissioning, these serviceability checks must be performed
at least twice annually. If no fault is found during two consecutive serviceability checks, then it is
possible to carry out serviceability checks once a year.

 

In the event that, for any reason, the dampers are found unfit to perform their function, this must
be clearly indicated. The operator is obliged to ensure that the damper is brought into a state
where it is able to perform its function again and during this time must provide fire protection in
another sufficient way.

 

The  results  of  regular  inspections,  deficiencies  found  and  all  important  facts  concerning  the
dampers function must be entered in the "FIRE BOOK" and reported to the operator immediately.

 

Flange and bolt connections must be conductively connected during installation in accordance
with EN 332000-4-41, -4-47 and -5-54 for protection against dangerous contact. For conductive
connections, 2 pieces of fan-shaped washers in galvanised design are used, which are placed
under the head of one bolt and under the screwed-on nut.

 

Installation,  maintenance  and  serviceability  checks  of  dampers  may  only  be  performed  by
persons qualified for these activities, i.e. "AUTHORISED PERSONS" trained by the manufacturer.

 

The training is performed by MANDÍK, a.s. and issues a "CERTIFICATE" of professional compe-
tence, which is valid for 5 years and its extension is ensured by the "AUTHORISED PERSON"
themselves, directly with the trainer.

 

Upon the expiry of the validity of the "CERTIFICATE", it loses its validity and is excluded from the
trainer's registration.

 

Only professionals who take over the warranty for the work performed may be trained.

Prior to commissioning dampers after installation and during subsequent serviceability checks,
the following checks must be carried out:

 of a damper's correct installation, the damper's internal space, the damper

leaf, the bearing surfaces of the leaf and the silicone seal.

 loosen the cover by turning the wing nut and release

it from the locking bracket by moving the cover left or right. Then tilting and removing the cover
from its original position. In the case of a screw cap, loosen and remove the screws with washers
and remove the cap cover.

•  Checking the thermal fuse of the drive - the drive must be removed.
•  Checking  damper  closing  -  pressing  the  release  button  on  the  mechanism  will  release  the

closing  mechanism  and  move  the  sheet  to  the  "CLOSED"  position.  The  closing  must  be
vigorous, the leaf must be in the "CLOSED" position on the stops. If the damper closure is not
strong enough or the leaf is not in the "CLOSED" position, the mechanism must be replaced.

 

•  The  damper  leaf  is  moved  to  the  "OPEN"  position  by  the  mechanism's  lever  to  the  second
  extreme position, where it must be locked.

•  Inspection of the leaf movement to the emergency position "CLOSED" is performed after the

power  supply  to  the  servo-drive  is  interrupted  (e.g.  by  pressing  the  reset  button  on  the
thermoelectric starting device, by interrupting the power supply from the EFS).

•  The check for moving the leaf back to the "OPEN" position is performed after the supply voltage

has been restored (e.g. by releasing the reset button, restoring the power supply from the EFS).

 

For reliable operation of dampers, care must be taken to ensure that the closing mechanism and
the bearing surfaces of the leaf are not clogged with dust deposits, fibrous or sticky substances
and solvents.

Содержание FDMR

Страница 1: ......

Страница 2: ...cription 3 2 Design 3 3 Placement and Assembly 4 4 Dimensions 6 5 Electrical elements wiring diagram 11 6 Material surface protection 12 7 Product data 12 8 Logistic terms 12 9 Warranty 12 10 Installa...

Страница 3: ...designed for environments protected against weather conditions with climatic conditions in 3K5 class with temperature limitation 20 C to 50 C without condensation icing ice formation without water an...

Страница 4: ...damper using the button on the temperature sensor simulates fuse failure Using a special key supplied with the actuator the damper leaf can be manually adjusted to any position and the position secure...

Страница 5: ...closing Fire damper Damper blade Fire dividing construction Fire damper Damper blade Fire dividing construction Protected duct Fire damper Damper blade Fire dividing construction The fire damper can b...

Страница 6: ...ExPro TT 2 Body 2 damper 9 Inspection hole covering 3 Damper blade 10 Control lever 4 Electrical actuator Schischek ExMax 15BF 11 Pin with lever 5 Mechanical actuator Atex 12 Initiation button 6 Therm...

Страница 7: ...ExPro TT 2 Body 2 damper 9 Inspection hole covering 3 Damper blade 10 Control lever 4 Electrical actuator Schischek ExMax 15BF 11 Pin with lever 5 Mechanical actuator Atex 12 Initiation button 6 Therm...

Страница 8: ...Thermo electrical fuse ExPro TT 2 Damper blade 8 Inspection hole covering 3 Electrical actuator Schischek ExMax 15BF 9 Control lever 4 Mechanical actuator Atex 10 Pin with lever 5 Thermal fuse 11 Ini...

Страница 9: ...Thermo electrical fuse ExPro TT 2 Damper blade 8 Inspection hole covering 3 Electrical actuator Schischek ExMax 15BF 9 Control lever 4 Mechanical actuator Atex 10 Pin with lever 5 Thermal fuse 11 Ini...

Страница 10: ...side length 1000 mm FDMQ from 150x150 to 1500x800 FDMR from 100 to 800 mm FDMA PM 900 and 1000 Square damper flanges with a width of 30 mm are provided with oval holes in the corners The connection di...

Страница 11: ...e 21 a 22 Adjustment time drive reverse gear 30 s 10 s Ambient operating temperature Storage temperature 40 C 40 C at T6 40 C 50 C at T5 40 C 70 C Humidity 0 95 rH non condensing Connection optional a...

Страница 12: ...box freight vehicles no sharp shocks must occur and the ambient temperature must not exceed 40 C For handling during transport the dampers must be protected against mechanical damages and weather imp...

Страница 13: ...the AUTHORISED PERSON themselves directly with the trainer Upon the expiry of the validity of the CERTIFICATE it loses its validity and is excluded from the trainer s registration Only professionals...

Страница 14: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...

Отзывы: