26
Position:
1
Fire damper
2
Sandwich wall construction
3
Stuffing box (mineral stone wool
min. density 140 kg/m³
4
Fire protection coating th. 1 mm
5
Fire protection mastic th. 1 mm
6
Cement lime plate min. thickness 15 mm
min. density 870 kg/m³
7
Duct
Used materials - example:*
2
Paroc AST S th. 100 mm
3
Promapyr, Rockwool Steprock HD, Hilti CFS-CT B 1S 140/50
4
Promastop - P, K, Hilti CFS-CT
5
HILTI CFS-S ACR
* Fire resistant insulation and fire resistant board can be
replaced by another approved fire sealing system for
damper installation with equivalent material properties.
≥
100
Содержание FDMR 60
Страница 1: ......
Страница 28: ...28 Position 1 Fire damper 2 Solid shaft construction 3 Mortar or gypsum 4 Duct 100...