The fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages
of fire separating structures. The damper assembly procedures must be done so that all load transfer
from the fire separating constructions to the damper body is absolutely excluded. The back-to-back
air-conditioning piping must be suspended or supported so that all load transfer from the back-to-
back piping to the damper flanges is absolutely excluded. The gap between the installed damper and
the building structure must be perfectly filled with approved material all over its volume.
To provide the necessary space for access to the control device, all other items must be situated at
least 350 mm from the control parts of the damper. At least one inspection hole must be accessible.
The damper must be installed so that the damper blade (in closed position) is situated in the fire
separating structure - marked by the label BUILD-IN EDGE on the damper body. If such solution is
not  possible,  the  piping  between  the  fire  separating  structure  and  the  damper  blade  must  be
protected according to the certified installation method, see Section 6.
During the installation and plastering process, the control mechanism must be protected (covered)
against damage and pollution. The damper body should not be deformed during bricking in. Once
the  damper  is  built  in,  the  damper  blade  should  not  grind  on  the  damper  body  during  opening  or
closing.
The  distance  between  the  fire  damper  and  the  structure  (wall,  ceiling)  must  be  75  mm  at  the
minimum. If two or more dampers are to be installed in one fire separating structure, the distance
between adjacent dampers must be 200 mm at the minimum, according to EN 1366-2 paragraph
13.5. For admissible exceptions see Section 6.

Built in edge

300

190

50

50

50

400

"Wall edge sticker" indicates the recommended edge of installation of fire damper into the fire partition structure (wall).

The damper must be installed so that the entire damper blade - in the closed position - is located inside the fire separating structure

(wall) and at the same time the control mechanism and inspection openings are freely accessible.

Distance between dampers 200 mm is acc. to EN 1366-2.

FDMR 60 has option to by installed one next to each other,
so called "in assembly" installation.

Содержание FDMR 60

Страница 1: ......

Страница 2: ...ns 1 Description 3 2 Design 4 3 Communication and control devices 9 4 Dimensions weights and effective area 12 5 Placement and Assembly 15 6 Statement of installations 17 7 Suspension system 30 8 Pres...

Страница 3: ...hole can be set to the most advantageous position with respect to operation and handling of the control device by turning the damper a little in case of the spiro model of the dampers Damper character...

Страница 4: ...only in size of inner spring which closes the fire damper For the size of fire dampers is always assigned the size of mechanism It is not recommended to use different size of mechanism than given by t...

Страница 5: ...from OPEN position to CLOSED position takes 20 seconds at the maximum If the power supply is restored the blade can be in any position the actuating mechanism starts to move the damper blade to OPEN p...

Страница 6: ...5 ms Protection class II III Degree of protection IP 54 Running time motor spring return 60 s 20 s Ambient temperature normal duty safety duty non operating temperature 30 C 55 C The safe position wil...

Страница 7: ...from the central through BKN 230 24 goes through the same wiring to the actuating mechanism To simplify the connection the actuating mechanism BFL 24 T is equipped with connecting plugs that are inser...

Страница 8: ...Connection net motor terminal board cable 0 9 m with EURO plug type 26 6 pole connector 3 pole connector screw terminals for cable 2x1 5 mm 1 2 3 4 5 6 7 b a 1 1 2 BAT 1 Bridge has been installed by...

Страница 9: ...ilable Contacts showing operating and failure position of the damper are active when the damper is in the given position Function check can be done by pressing and holding the button RESET TEST for lo...

Страница 10: ...nd issues control commands Proper damper operation is indicated by two light LED diodes Control ON position OPERATION Control OFF position FAILURE If the fire damper do not reach the given position in...

Страница 11: ...11 Nominal voltage AC 24 V 50 60Hz Power consumption 3 5 W Dimensioning 5 5 VA Protection Class III Degree of protection IP 30 Ambient temperature 0 50 C Connection terminal 2 x 1 5 mm...

Страница 12: ...3 3 2 0 0085 15 BFL M1 3 4 3 3 0 0103 15 BFL M1 3 5 3 5 0 0123 15 BFL M1 3 9 3 8 0 0166 15 BFL M1 4 2 4 1 0 0215 15 BFL M1 4 5 4 5 0 0275 15 BFL M1 8 4 8 4 7 0 0354 15 BFL M2 23 5 3 5 2 0 0462 15 BFL...

Страница 13: ...ection hole covering 5 Sensor sticker 6 Hole for camera 300 50 120 D 110 400 180 50 Position 1 Damper casing 2 Actuating mechanism 3 Damper blade 4 Inspection hole covering 5 BAT thermoelectrical star...

Страница 14: ...overlaps For the design 60 with BKN supply and communication device add to weight of the damper with an actuating mechanism from the Tab 4 4 1 the weight of BKN 0 5 kg Side without act mechanism a Ta...

Страница 15: ...cture and the damper blade must be protected according to the certified installation method see Section 6 During the installation and plastering process the control mechanism must be protected covered...

Страница 16: ...te with minimum thickness 100 mm or into solid ceiling construction made e g of normal concrete with minimum thickness 110 mm or porous concrete with minimum thickness 125 mm The fire damper can be in...

Страница 17: ...0 Mineral wool stuffing box and fire protection mastic ISOVER_ULTIMATE PROTECT 23 110 Concrete 125 Aerated concrete Mortar or gypsum 24 Stuffing box and fire protection mastic 24 Mineral wool mortar o...

Страница 18: ...ne wool min density 140 kg m 4 Fire protection mastic min thickness 1 mm Used materials example 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT 50 25 100 Fire res...

Страница 19: ...g box mineral stone wool min density 140 kg m Gap between damper and construction is filled by mortar or gypsum and mineral wool Wool is fixed to damper body and construction by fire protection mastic...

Страница 20: ...ning and insulation materials can be replaced by another approved fire sealing system with equivalent properties The maximum distance of the fire damper from the structure is not limited and according...

Страница 21: ...type of construction 4 Stuffing box mineral stone wool min density 140 kg m 5 Fire protection mastic min thickness 1 mm Fire resistant insulation and fire resistant board can be replaced by another ap...

Страница 22: ...ponding length Distance between screws 200 mm Installation opening has to be reinforced by profile UW CW Profil is fixed by screws 3 5 mm with corre sponding length Distance between screws 200 mm Gap...

Страница 23: ...imeter Position 1 Fire damper 2 Gypsum plate 3 Mineral wool type depending on the type of construction 4 Stuffing box mineral stone wool min density 140 kg m 5 Fire protection mastic min thickness 1 m...

Страница 24: ...stone wool min density 140 kg m 4 Fire protection mastic min thickness 1 mm Fire resistant insulation and fire resistant board can be replaced by another approved fire sealing system for damper instal...

Страница 25: ...e and insulation materials can be replaced by another approved fire sealing system for damper installation with equivalent material properties Depends on the distance of the flap from the construction...

Страница 26: ...nt lime plate min thickness 15 mm min density 870 kg m 7 Duct Used materials example 2 Paroc AST S th 100 mm 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT 5 HIL...

Страница 27: ...7 Cement lime plate min thickness 15 mm min density 870 kg m 8 Duct Used materials example 2 Paroc AST S th 100 mm 3 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140 50 4 Promastop P K Hilti CFS CT...

Страница 28: ...28 Position 1 Fire damper 2 Solid shaft construction 3 Mortar or gypsum 4 Duct 100...

Страница 29: ...of construction 4 Stuffing box mineral stone wool min density 140 kg m 5 Fire protection mastic min thickness 1 mm 6 Duct Used materials example 4 Promapyr Rockwool Steprock HD Hilti CFS CT B 1S 140...

Страница 30: ...ng wall M8 366 22 44 M10 58 35 70 M12 84 3 52 104 M14 115 70 140 M16 157 96 192 M18 192 117 234 M20 245 150 300 Position 1 Threaded rod M8 M20 2 Nut 3 Washer 4 Coupling Nut 5 Anchor 6 Hinge plate min...

Страница 31: ...anging round pipes 7 Threaded rod with anchor for anchoring connecting pipe to the ceiling 8 Fixing element steel holder for connecting pipe to the wall recommended type 9 Nut M8 with anchor 10 Screw...

Страница 32: ...ring for hanging round pipes 6 Threaded rod with anchor for anchoring connecting pipe to the wall 7 Fixing element steel holder for connecting pipe to the ceiling recommended type 8 Nut M8 with ancho...

Страница 33: ...es 7 Threaded rod with anchor for anchoring connecting pipe to the ceiling 8 Fixing element steel holder for connecting pipe to the wall recommended type 9 Nut M8 with anchor 10 Screw with hexagon hea...

Страница 34: ...g round pipes 6 Threaded rod with anchor for anchoring connecting pipe to the wall 7 Fixing element steel holder for connecting pipe to the ceiling recommended type 8 Nut M8 with anchor 9 Holes for ri...

Страница 35: ...ction see fig 36 Fire dampers can be suspended by using threaded rods and a mounting profiles Load the suspension system depend on weight of the fire damper Damper can be suspended from the ceiling co...

Страница 36: ...per must be firmly connected with extension piece by screws or rivets Position 1 Fire damper 2 Damping pad 3 Extension piece 4 Threaded rod 5 Mounting rail 6 Nut 7 Washer 8 Screw connection 9 Mounting...

Страница 37: ...the damper body is absolutely excluded Back to back air conditioning piping must be hung or supported so as all load transfer from the back to back piping to the damper is absolutely excluded Threaded...

Страница 38: ...n p w 2 p Pa presure loss w m s air flow speed in nominal damper section kg m air density coefficient of local pressure loss for the nominal damper section see Tab 9 1 1 Determination of pressure loss...

Страница 39: ...KA dB correction to the weight filter A see Tab 10 3 2 Level of acoustic output in octave ranges LWoct LW1 10 log S Lrel LWoct dB spectrum of acoustic output in octave range LW1 dB level of acoustic...

Страница 40: ...9 56 1 59 3 61 5 63 3 66 4 68 6 70 4 71 8 73 48 1 53 5 56 6 58 9 62 64 3 66 69 1 71 4 73 1 74 5 75 7 50 6 56 59 1 61 4 64 5 66 7 68 5 71 6 73 9 75 6 77 78 2 52 8 58 2 61 4 63 6 66 8 69 70 7 73 9 76 1...

Страница 41: ...e selector pin with lever 4 Mechanical components entering the interior of damper body lower sheet of mechanics lock holder 1 lock lever 2 lock spring 8 dia stopper pin mechanics pin 5 Inspection hole...

Страница 42: ...nstruments according to the standard of non tolerated sizes used in air conditioning industry Interoperational checks of components and main sizes are carried out according to drawing documentation Th...

Страница 43: ...bolt and under the screwed nut Before entering the dampers into operation after their assembly and by sequential checks the following checks must be carried out Visual inspection of proper damper int...

Страница 44: ...spring For the designs with actuating mechanisms the following checks must be carried out Check the shift of the blade to CLOSED failure position after cutting off the power supply to the actuating m...

Страница 45: ...munication and supply device BKN 230 24 and actuating mechanism BFL 24 T ST 60 Manual and thermal with two terminal switches OPEN CLOSED 80 Spare parts are supplied only on basis of an order If trippi...

Страница 46: ...www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz www mandik com WEIGHT kg Dob sk 550 267 24 Hostomice Czech Republic MAND K a s ACTUATIN...

Отзывы: