FDMQ 120 - Fire damper
Page 26
Version 2022-12-20
TPM 166/22
EIS 120
5
0
..
.2
0
0
≥
100
Solid wall construction - Ablative Coated Batt
1
FDMQ 120
2
Solid wall construction
3
Ablative Coated Batt (e.g. Firestop Board HILTI CFS-CT B 1S 140/50 - min. density 140 kg/m
3
+ Firestop acrylic
sealant HILTI CFS-S ACR or equivalent)
4
Fire stop coating thickness 1 mm (e.g. HILTI CFS-CT, PROMASTOP-CC or equivalent)
5
Duct
6
Protective cladding boards - (not part of the damper) but must be used as part of the penetration filling. It can be
ordered from MANDÍK as an accessory (e.g. PROMATECT-MST th. 30 mm - min. density 750 kg/m
3
or equivalent)
7
Fire resistant mastic - fill the gap on both sides of the fire separation construction and around the perimeter of
penetration and damper body. (e.g. HILTI CFS-S ACR)
8
Fixing profile with threaded rod
■
For connection following duct