15. Entry into service and revisions
15.1.
Before entering the dampers into operation after assembly and after sequential revisions, checks
and functionality tests of all designs including operation of the electrical components must be
done. After entering into operation, these revisions must be done according to requirement set
by national regulations.
15.1.1.
In case that dampers are found unable to serve for their function for any cause, it must be clearly
marked. The operator is obliged to ensure so that the damper is put into condition in which it is
able to function and meanwhile he is obliged to provide the fire protection another appropriate
way.
15.2.
Before entering the dampers into operation after their assembly and by sequential checks, the
following checks must be carried out.
15.2.1.
Visual inspection of proper damper integration, inside damper area, damper blade, contact
surfaces and silicon sealing.
15.2.2.
Inspection hole disassembly: release the covering lid by unscrewing screws. Then tilt remove lid
from its original position.
15.1.2.
Results of regular checks, imperfections found and all-important facts connected with the damper
function must be recorded in the "FIRE BOOK" and immediately reported to the operator.
15.2.3.
Check of blade displacement into the breakdown position "CLOSED" can be done after cutting
off the actuating mechanism supply (e.g. by pressing the RESET button at the thermoelectrical
starting mechanism BAE 72B-S - only FDMC or cutting off the supply from ELECTRICAL FIRE
SIGNALISATION). Check of blade displacement back into the "OPEN" position can be done after
restoration of power supply (e.g. By releasing the RESET button - only FDMC or restoration of
supply from ELECTRICAL FIRE SIGNALISATION).