background image

TPM 083/12

6

Park Allé 366, DK-2605 Brondby
Telefon 70 20 19 11; E-mail:[email protected]

Tab. 3.2.1.  Weight and  effective area

 Size

  D

a

Weight

Effective area

 S

ef

 [m

2

]

Actuating mechanism

100

-

3,1

0,0036

BLF

125

-

3,4

0,0068

BLF

140

-

3,6

0,0092

BLF

150

-

3,7

0,0109

BLF

160

-

3,8

0,0129

BLF

180

-

4,1

0,0172

BLF

200

-

4,4

0,0222

BLF

225

-

4,7

0,0293

BLF

250

9

5,5

0,0374

BLF

280

24

6,0

0,0484

BLF

315

41,5

6,6

0,0630

BLF

350

59

7,0

0,0793

BLF

355

61,5

7,3

0,0821

BLF

400

84

8,2

0,1065

BLF

3.2. 

 

Weight and  effective area

4. Placement and Assembly

4.1. 

 

Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages
of fire separating constructions. Damper assembly procedures must be done so as all load
transfer from the fire separating constructions to the damper body is absolutely excluded.
Back-to-back air-conditioning piping must be hung or supported so as all load transfer from the
back-to-back piping to the damper is absolutely excluded.

3.3. 

 

For fire damper the open damper blade overlaps the damper body from dimension    250 by the
“a” value. These values are specified in the Tab. 3.2.1

 

Value has to be respected when projecting related air-conditioning piping.

Fig. 4 

Value “a”

Содержание FDMC

Страница 1: ...FDMC FDMC SRD TPM 083 12 DK VALID FROM 15 1 2012 FIRE DAMPER AND FIRE DAMPER SMOKE RELIEF...

Страница 2: ...ription 3 2 Design 4 3 Dimensions weights 5 4 Placement and Assembly 6 5 Statement of installations 8 III TECHNICAL DATA 9 6 Pressure loss 9 7 Coefficient of local pressure loss 10 8 Noise data 10 9 E...

Страница 3: ...N 13501 3 and tested acc EN 1366 2 1 5 Dampers have one inspection hole since the shutting device and the inspection hole can be set into the most advantageous position with respect to the operation a...

Страница 4: ...of the actuating mechanism These fuses are activated when temperature 72 C has been exceeded the fuse Tf1 when the temperature around the damper and the fuses Tf2 Tf3 when the temperature inside the...

Страница 5: ...1 E mail oeland oeland dk Position 1 Damper body 4 BAE 72B S thermoelectrical starting mechanism 2 Damper blade 5 Inspection hole covering 3 Actuating mechanism Fig 2 Fire damper FDMC Fig 3 Fire dampe...

Страница 6: ...a 4 Placement and Assembly 4 1 Fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions Damper assembly procedures must be...

Страница 7: ...mper body during opening or closing 4 7 Installation opening dimensions 4 2 To provide needed access space to the control device all other objects must be situated at least 350 mm from the control par...

Страница 8: ...tallation EIS 60 8 Damper installed on a solid ceiling construction Space between damper and ceiling is filled by mortar gypsum or another approved fire sealing system for damper installation EIS 60 9...

Страница 9: ...min density 800 kg m3 or another approved fire sealing system for damper installation Fig 8 Installation on a gypsum wall construction 2 1 2 1 Fig 9 Installation on a ceiling wall construction 1 2 2 1...

Страница 10: ...t solid wall construction 4 Position 1 Fire damper FDMC 3 Duct 2 Mortar or gypsum with min density 800 kg m3 or another approved fire sealing system for damper installation 4 Installation shaft 3 1 2...

Страница 11: ...oss for the nominal damper section see Tab 7 1 1 III TECHNICAL DATA 6 2 Determination of pressure loss by using diagram 6 2 1 1 2 kg m 3 Diagram 6 2 1 Pressure losses for air density 1 2 kg m 3 7 1 Co...

Страница 12: ...see Tab 8 3 3 LWoct LW1 10 log S Lrel 8 3 Table of acoustics values Tab 8 3 1 Level of acoustic output LW1 related to the 1 m2 section w m s 1 0 1 0 2 0 3 0 4 0 6 0 8 1 1 5 2 2 5 3 3 5 2 9 0 11 5 14 7...

Страница 13: ...l 48 8 10 log 0 0374 11 5 23 1 dB Tab 8 3 2 Correction to the weight filter A w m s 1 2 3 4 5 6 7 8 9 10 11 12 KA dB 15 0 11 8 9 8 8 4 7 3 6 4 5 7 5 0 4 5 4 0 3 6 Tab 8 3 3 Relative level expressing t...

Страница 14: ...oring holding 5 W 2 5 W Dimensioning 7 VA Imax 5 8 A 5 ms Protection Class III Degree of protection IP 54 Running time motor spring return 40 75 s 20 s Ambient Temperature normal duty safety duty non...

Страница 15: ...e fire damper function it is necessary to avoid blocking the closing mechanism and contact surfaces with collected dust fibre and sticky materials and solvents 13 Logistic terms 13 1 Dampers are trans...

Страница 16: ...ile he is obliged to provide the fire protection another appropriate way 15 2 Before entering the dampers into operation after their assembly and by sequential checks the following checks must be carr...

Отзывы:

Похожие инструкции для FDMC