50
Mounting to the ceiling wall
M8
36,6
22
44
M10
58,0
35
70
M12
843
52
104
M14
115
70
140
M16
157
96
192
M18
192
117
234
M20
245
150
300
120
2x
Ø
9
M
8 -
M
16
50
4x
Ø
9
M20
100
150
Position:
1
Threaded rod M8 – M20
2
Nut
3
Washer
4
Coupling Nut
5
Anchor
6
Hinge plate - min. thickness 10 mm
80
Horizontal installation
Fire dampers can be suspended by using threaded rods and a mounting profiles. Load the
suspension system depend on weight of the fire damper.
Damper assembly procedures must be done so as all load transfer from the fire separating
constructions to the damper body is absolutely excluded. Back-to-back air-conditioning piping
must be hung or supported so as all load transfer from the back-to-back piping to the damper is
absolutely excluded.
Threaded rods longer than 1,5 m require fire-resistant insulation.
Threaded rod fixing to the ceiling construction - see fig. 60
Содержание FDMA
Страница 1: ......