61
≥
100
POSITION:
1
Fire damper FDMA PM with
Installation frame E1, R1
2
Gypsum plate
3
Mineral wool (type depending
on the type of construction)
4
Mineral stone wool min. Den-
sity 140 kg/m
5
Flange connection
≥
100
≥
100
20
20
20
20
A = max. 1000 mm
≥
100
Dimensions
Number
ZB1
Number
ZH1
A1,B1,D1 ≤ 400
1
1
400 <
A1,B1,D1 ≤ 800
2
2
800 <
A1,D1 ≤ 1200
3
3
1200 <
A1,D1 ≤ 1600
4
4
1600 <
A1,D1 ≤ 2000
5
5
2000 <
A1 ≤ 2400
6
6
2400 <
A1 ≤ 2800
7
7
2800 <
A1 ≤ 3000
8
8
●
Fire damper FDMA PM-C - installation opening dimensions
a x b = (2x(A + 85 mm) + 20 mm) x (B + 85 mm)
or a x b = (A + 85 mm) x (2x(B + 85 mm) + 20 mm)
●
Fire damper FDMA PM-C - installation opening dimensions
a x b = (2x(D + 141 mm) + 20 mm) x (D + 141 mm)
or a x b = (D + 141 mm) x (2x(D + 141 mm) + 20 mm)
●
Gap between frame and damper body and frame and construction
must be filled by glue (PROMAT K84)
●
Fire damper FDMA PM-C - distance between dampers 104 mm
●
Fire damper FDMA PM-K - distance between dampers 160 mm
●
Flange to flange connection - Up to four dampers can be installed
It is possible to use
corresponding number of
holes and screws
Installation opening has to be
reinforced by profile (UW, CW).
Profil is fixed by screws ≥3,5 mm
with corresponding length. Distance
between screws ≤200 mm.
Installation opening has to be reinforced by
profile (UW, CW). Profil is fixed by screws
≥3,5 mm with corresponding length.
Distance between screws ≤200 mm.
Installation opening
has to be reinforced
by profile (UW, CW).
Profil is fixed by
screws ≥3,5 mm with
corresponding length.
Distance between
screws ≤200 mm.
Installation opening
has to be reinforced
by profile (UW, CW).
Profil is fixed by
screws ≥3,5 mm with
corresponding length.
Distance between
screws ≤200 mm.