41
≥
100
≥
100
20
20
20
20
A = max. 1000 mm
POSITION:
1
Fire damper FDMA PM with
installation frame E1, R1
2
Solid wall construction
3
Mineral stone wool min.
Density 140 kg/m
4
Flange connection
≥
100
≥
100
Dimensions
Number
ZB1
Number
ZH1
A1,B1,D1 ≤ 400
1
1
400 <
A1,B1,D1 ≤ 800
2
2
800 <
A1,D1 ≤ 1200
3
3
1200 < A
1,D1 ≤ 1600
4
4
1600 <
A1,D1 ≤ 2000
5
5
2000 <
A1 ≤ 2400
6
6
2400 <
A1 ≤ 2800
7
7
2800 <
A1 ≤ 3000
8
8
It is possible to use
corresponding number of
holes and screws
●
Fire damper FDMA PM-C - installation opening dimensions
a x b = (2x(A + 85 mm) + 20 mm) x (B + 85 mm)
or a x b = (A + 85 mm) x (2x(B + 85 mm) + 20 mm)
●
Fire damper FDMA PM-C - installation opening dimensions
a x b = (2x(D + 141 mm) + 20 mm) x (D + 141 mm)
or. a x b = (D + 141 mm) x (2x(D + 141 mm) + 20 mm)
●
Gap between frame and damper body and frame and construction
must be filled by glue (PROMAT K84)
●
Fire damper FDMA PM-C - distance between dampers 104 mm
●
Fire damper FDMA PM-K - distance between dampers 160 mm
●
Flange to flange connection - Up to four dampers can be installed