TPM 092/13
10
1
2
POSITION
1
Fire damper FDMD
2
Mortar or gypsum with min.
density 800 kg/m
3
2
Fig. 9
Installation in a solid wall construction
Fig. 10 Installation in a solid wall construction
Fig. 11 Installation in a solid wall construction
1
1
2
POSITION
1
Fire damper FDMD
2
Stuffing box (mineral stone wool
min. density 140 kg/m
3
)
3
Fire protection mastic min.
thickness 1 mm
2
1
3
3
Used materials - example*:
2
Promapyr, Rockwool Steprock HD
3
Promastop - P, K
* Stuffing box and fire protection mastic can be replaced by another approved
fire sealing system for damper installation with equivalent material properties.
1
2
POSITION
1
Fire damper FDMD
2
Fire resistant board
3
Fire stop coating thickness 1 mm
2
1
3
3
Used materials - example*:
2
Hilti CP673 PF
3
Hilti CP673