Operator Start-up
WARNING
To reduce risk of SEVERE INJURY or DEATH to persons:
•
Personnel should keep away from a door in motion and keep the moving door in sight until it is
completely closed or opened. NO ONE SHOULD CROSS THE PATH OF A MOVING DOOR.
•
Never go under a stopped, partially opened door.
1. Turn power ON.
2. Use on-board, wall-button station (Open/Close/Stop), external entrapment device or jumper wires for testing,
see Table 9.
Table 9 - Start-up and Testing Guide
Test
Door Position
Action
Door Response
LED Status
Open
Door at 6” from the
closed position
1. Press “OPEN”.
2. Check if door is stopped
by Open limit switch.
3. If required, re-adjust
Open limit, as shown in
Figure 13, p.13.
Door should open instantly.
“Open Limit”
LED is ON
Close
Door at fully open
position
1. Press “CLOSE”.
2. Check if door is stopped
by Close limit switch.
3. If required, re-adjust
Close limit, as shown in
Figure 13, p.13.
- C2 mode:
(selector switch on
C2=0).
Door should close as long as the
close button is activated.
- B2 mode
:
(selector switch on
B2=1).
Door should close instantly.
“Close Limit”
LED is ON
Sense
Edge
A) Door at fully
closed position
Activate external entrapment
device
OR
Momentarily touch #3 & #5
on the main terminal with a
jumper wire.
Door should stay at closed
position.
“SENS” LED
is ON as
long as the
contact is
maintained
B) Door is closing
(movement)
Door should stop and then
reverse to fully opened position.
Open &
Close
(single-
button
radio)
A) Door at fully
opened position
Activate the single-button
transmitter
OR
Momentarily touch #3 & #4
on the main terminal with a
jumper wire.
Door should close.
“O/C” LED is
ON as long
as the
contact is
maintained
(+/- 2 sec)
B) Door at fully
closed position
Door should open.
C) Door is closing
(movement)
Door should reverse to fully
opened position.