Specification:
Power Supply: 3 AA size 1.5V batteries
Sensitivity & Time:
30ppm, alarms within 120 minutes
50ppm, alarms within 60~90 minutes
100ppm, alarms within 10~40 minutes
300ppm, alarms within 3 minutes
Standby Current: <50Ua (without LCD); <200uA (With LCD)
Alarm Current: 75mA
Operation Ambient Condition: 15~35°C, 20~90R R.H.
Installation Instructions
Step 1
Installation Guide:
IMPORTANT: THIS ALARM MUST BE MOUNTED ON A WALL. INSTALL ONLY AS
DETAILED!
A. Recommended Installation Locations:
We recommend the installation of a CO Alarm in the following locations.
For maximum protection we suggest an alarm be installed on each level of a multilevel
home including every bedroom, hallways, finished attics and basements. Put alarm at both
ends of bedroom hallway or large room if hallway or room is more than 30ft. (9,1m) long. If
you have only one alarm, ensure it is placed in the hallway outside of the main sleeping
area, or in the main bedroom. Verify the alarm can be heard in all sleeping areas.
Locate an alarm I every room where someone sleeps with the door closed. The closed
door may prevent the alarm from waking the sleeper. Mounting the alarm on the ceiling in
the center of the room places it closest to all points in the room. Ceiling mounting is
preferred in ordinary residential construction. When mounting an alarm on the ceiling,
locate it at a minimum of 4” (10cm) from the side wall (see Diagram A). if installing the
alarm on the wall, at a minimum of 4” (10 cm) and a maximum of 12” (30.5 cm) below the
ceiling (see Diagram below).
10/22