15
The numerical value below the OPU will flash. Press and hold the inquiring key
for
more than half a second (less than 2 seconds), select the numerical value in
accordance with “OPU” function. The provided voltages are 208V,220V, 230V, 240V
you can choose anyone by yourself (The default is 220v).
③
Confirm the output voltage selecting interface. After selecting numerical value,
press and hold the function setting key
for more than half a second (less than 2
seconds). Now, the OPU setting function is completed and the numerical value below
the “OPU” will light without flash.
④
Exit from the setting interface. Press and hold function setting key
for more
than half a second (less than 2 seconds), exit from the setting interface and return to
main interface.
NOTE:When setting the output voltage, you’d better cut off the load of the UPS first.
4.3.4
Battery Pack (EBP) number and type setting(4)
①
Enter the setting interface. Press and hold the function setting key
for more than
2 seconds, then come to setting interface, Press and hold the scroll key
for
more than half a second(less than 2 seconds), select the function setting, choose
battery setting interface, at the moment, the letters “bAt” will flash.
②
Enter the battery setting interface. Press and hold the function setting key
for
more than half a second(less than 2 seconds), then come to setting interface of
battery, the letters “bAt” will stop flashing. The numerical value below the “bAt” will
flash. Press and hold the scroll key
for more than half a second (less than 2
seconds), select the numerical value in accordance with the real connected battery
packs.
③
Confirm the battery packs setting interface
。