BOXER SERIES10-20 KVA
INSTALLATION
AG-SD-109 Publishing Date: 13.10.2015 Revision No: 0 Rev. Date:
Battery rooms should be properly ventilated.
Shelves will be accessible in touch if batteries are in battery room. Therefore, please
keep restricted accessing to battery rooms. Use necessary safety writings and strips.
Especially, for the external cabinet batteries system of UPS, fuses must definitely be used. These
fuses must be mounted as close as possible to the batteries. This closeness will increase the
electrical operation safety with the battery.
BOXER EXTERNAL BATTERY CABINET CONFIGURATION
Device Rating (kVA)
10
15
20
Batteries in series
31
31
31
Independent Group Number
2
2
2
Total number of Battery
62
62
62
I_charge_max@V_bat._max(A)
2,3
3,4
4,5
I_bat._max@V_bat._cut off(A)
13
19
26
Recommended external cabinet fuse (A)
20
32
40
External battery cabinet and battery room applications are given below as an example. The
application form may vary according to the customer.