2. 

SPECIFICATIONS

 

 

 

 

 

 

 

 

Current Settings 

0 - 1000mA 

Current Selection 

Knob 

Phase Start Selection; 

 

0˚ 

Yes 

180˚ 

Yes 

Phase Polarity Trip Indicator 

Yes 

Operating Voltage (L-E) 

110Vac to 317Vac 

Timer Resolution 

1mS 

Timer Accuracy 

1mS 

Current Accuracy 

1% & 2mA 

Current Resolution 

1mA 

Voltmeter Accuracy 

5% 

Voltmeter Resolution 

1V 

Operating Temperature 

-5˚C - 45˚C 

Storage Temperature 

-10˚ - 47˚C 

Battery  

8 x AA batteries 

Maximum Current Specified at 

317Vac 

 

 

7. 

RCCB/ELCB TESTING - TIME DELAY - 

 

 

Turn Instrument “ON” by pressing the “ON” button. 

 

The L.C.D display will come to the following Screen. 

 
 

 
 

 

 

 

 

 
 

 

 
 

 

 

 

 

   - Instantaneous 

  

*  - Time Delay 

Dial Starting 

Current 125mA 

Push Select to change Selection 

To Instantaneous, then Press “TEST” 

Dial the Starting Current of the 

Instantaneous Test using the knob 

Positive 
Start Edge 

Select the Positive or negative 

Start Edge using the Select Button 

Connect Leads 

To Earth & Phase 

Connect Leads 

The Test will start 

 

V = 317V  T= 4.023s 

 

 I = 125mA 

Test in Progress 

Between leads is 317V 

 

V = 317V + T = 12.435s 

 

 I = 125mA HOLD → TRP 

TRP = Tripped, Display on Hold 

At 12.435s Tripped on + edge of signal 

 
 
 
 

 

 

 

 

 