Majestic Royalton Series • BE36/42 • 4044-197 Installation Manual • Rev J •  09/18

I.  Termination Cap Requirements

•  Install a cap approved and listed for this fireplace system.

•  Locate cap where it will not become plugged by snow 

or other materials.

•  Locate cap away from trees or other structures.

•  The bottom of the termination cap must be at least 3 ft 

(.91 m) above the roof AND at least 2 ft (.61 m) above 

any portion of roof within 10 ft (3.05 m). 

J.  Install Termination Cap

Install the chimney sections up through the chase enclo

-

sure.

  Caulk the overlap seam of any exposed pipe sections 

that are located above the roof line to prevent leaks.

  Refer to termination cap instructions.

 WARNING! 

Risk of Fire! 

The minimum overlap of cap 

to pipe (as shown in the following illustrations) MUST 

be met or chimney may separate from cap. Separation 

allows sparks, heat and embers to escape.

 NOTICE: 

Paint the termination cap with a rust-resistant 

paint to protect against the effects of corrosion on those 

parts exposed to the weather.

Storm

Collar

Chimney

Pipe

Chase Top

Termination

Cap

Chase

6 in. (153 mm)

Minimum top of

chase to top of

chimney pipe

Collar

2 in. (51 mm)

Minimum Height

Do NOT

block air holes

Caulk gaps between 

storm collar & pipe,

and storm collar

& chase top.

Termination cap pipe and chimney section must be snapped 

together to maintain an overlap of 1-1/2 in. (38 mm).

Slip

storm collar

around chimney pipe

before termination 

cap pipe is snapped 

into the chimney 

pipe.

Figure 5.10  Installing a TR344 Round Termination Cap

Figure 5.11  Installing a TR342-B Round Telescoping Termination 

Cap

Figure 5.12  Installing an ST375 Square Termination Cap

Storm

Collar

Chimney

Pipe

Chase Top

Termination

Cap

Chase

4 3/4 in. (121 mm)

Maximum

Collar

2 in. (51 mm)

Minimum Height

Caulk gaps between 

storm collar & pipe,

and storm collar

& chase top.

Do NOT 

block air 

holes

3 clip brackets.

Slip over chase collar

and attach with screws

provided.

Assemble

storm collar

around extended  

termination cap 

pipe

once cap is 

installed.

The last section of pipe must 

stop between 2 in. (51 mm) 

above the top of the chase and 

4 3/4 in. (121 mm) below the 

top of the chase.

2 in. (51 mm)

maximum

Chimney

Pipe

Chase Top

Termination Cap

Chase

Collar

2 in. (51 mm)

Minimum Height

Place waterproof 

caulk or sealer under 

each flange of the 

termination cap and 

on top of each screw 

to help prevent leaks. 

Flange

2 in. (51 mm)

maximum

4 3/4 in. (121 mm)

maximum

The last section of pipe 

must stop between 2 in. (51 

mm) above the top of the 

chase and 4 3/4 in. (121 

mm) below the top of the 

chase.

Содержание Royalton BE36

Страница 1: ...d other flammable materials away INSTALLER Leave this manual with party responsible for use and operation OWNER Retain this manual for future reference BE36 BE42 NOTICE DO NOT discard this manual DO N...

Страница 2: ...e 11 D Frame the Fireplace 12 E Secure and Level the Fireplace 12 F Protective Metal Hearth Strips 13 G Outside Air Kit optional 14 4 Chimney and Termination Requirements A Chimney Requirements 15 B O...

Страница 3: ...oud is installed properly per instructions Fi i hi S ti 7 P 27 Dealer Distributor Phone Serial Roof flashing installed Termination installed Hearth Home Technologies recommends the following Comments...

Страница 4: ...e following materials Wood Compressed paper Plant fibers Plastic Plywood OSB Sheet rock drywall Any material that can ignite and burn flame proofed or not plastered or un plastered 1 Product Specific...

Страница 5: ...ion cap Chimney penetrates roof preferably without affecting roof rafters Offset Return with hanger straps Framing headed off in ceiling joists Enclosed space above and around fireplace Mantel and sur...

Страница 6: ...Clearances Section 3 NOTICE A minimum 1 2 in air clearance at the back and sides of the fireplace assembly must be main tained Chimney sections at any level require a 2 in minimum air space clearance...

Страница 7: ...ighest point of the roof Wind loading possible Multi level Roofs Windward Leeward Recommended Location Above peak Recommended Insulated exterior chase in cooler climates Recommended Location Above pea...

Страница 8: ...Keep fire place dry Remove fireplace and components from packaging and inspect for damage Vent system components and doors are shipped in separate packages Report to your dealer any parts damaged in s...

Страница 9: ...in 359 mm 18 3 4 in 476 mm 21 in 533 mm 7 1 2 in 191 mm 9 1 4 in 235 mm 7 1 2 in 191 mm Gas Knockout Outside Air 9 1 4 in 235 mm Gas Knockout 7 1 2 in 191 mm 39 1 2 in 1003 mm C D B 21 3 8 in 543 mm...

Страница 10: ...als Minimum Clearances to Combustibles WITHIN ENCLOSURE AREA Fireplace to backwall 1 2 in 13 mm Fireplace to sidewall 1 2 in 13 mm Top standoffs to header 0 in 0 mm Door opening to sidewall 12 in 305...

Страница 11: ...gure 3 3 Chase Assembly 1 2 3 1 Fireplace and chimney enclosed in an exterior chase 2 Chimney offset through exterior wall and enclosed in chase 3 Chase constructed on roof Note In cooler climates all...

Страница 12: ...sed insulation Secure insulation and vapor barriers Provide minimum air space clearances at the sides and back of the fireplace assembly E Secure and Level the Fireplace This fireplace may be placed o...

Страница 13: ...under front edge of fireplace Overlap strips in the middle of fireplace opening by 1 in 25 mm minimum Metal strips must extend beyond the front and sides of the fireplace opening by at least 2 in 51 m...

Страница 14: ...inlet hood and the house with silicone to prevent air infiltration CAUTION Risk of Cuts Abrasions Wear protective gloves and safety glasses during installation Sheet metal edges are sharp CAUTION Risk...

Страница 15: ...from the fireplace or at any chimney joint A Chimney Requirements Vertical distances are measured from the base of the fireplace as shown in Figure 4 1 4 Chimney and Termination Requirements Table 4...

Страница 16: ...offset return You determine from the table that you need 34 1 8 in 867 mm Dimension B between the offset and return The chimney component that best fits your application is one SL324 15 degree 30 deg...

Страница 17: ...See illustration above B Gas Termination Cap A Perpendicular Wall If using decorative cap cover s this distance may need to be increased Refer to the installation instructions supplied with the decor...

Страница 18: ...vertical Lock chimney sections together firmly to resist movement Ceiling firestops are required where chimney passes through ceiling or floor Support straps for offsets not shown must be secured to...

Страница 19: ...turns to chimney sections Insert the screws provided through the predrilled holes Do NOT penetrate inner flue Secure chimney returns with hanger straps provided fasten to studs or joists Vertical stra...

Страница 20: ...ming Note Use same dimensional lumber for framing ceiling firestop and joists 2 in 51mm clearance 2 in 51mm clearance WARNING Risk of Fire DO NOT seal area between firestop opening and chimney pipe ex...

Страница 21: ...n 90 Figure 5 5 Prepare Attic Insulation Shield F Install Attic Insulation Shield WARNING Risk of Fire You MUST install an attic insu lation shield when there is any possibility of insulation or other...

Страница 22: ...m Turn down Drip Edge Chase 2 in 51 mm Collar on Chase Top 018 26 ga min Galvanized Chase Top Figure 5 9 Chase Top Construction H Install Chase Chase Top You MUST use a chase top in a chase installati...

Страница 23: ...o NOT block air holes Caulk gaps between storm collar pipe and storm collar chase top Termination cap pipe and chimney section must be snapped together to maintain an overlap of 1 1 2 in 38 mm Slip st...

Страница 24: ...Collar 2 in 51 mm Minimum Height Remove 2 screws from front back to lift the top off Place waterproof sealer under each flange of the termination cap and on top of each screw to help prevent leaks Th...

Страница 25: ...stems and termination caps 3 in 76 mm minimum Min Base Dim Min Base Dim Min Top Dim Min Top Dim Min Opening Width Min Opening Width Radiation Shield 14 1 2 in 368 mm maximum height TS345 TR344 TR342B...

Страница 26: ...se Top Radiation Shield 3 in 76 mm Radiation Shield Height Termination Cap Figure 65 Roofed Style Shroud Dimensions 3 Roofed Style Shroud Radiation shield required 2 Mailbox Style Shroud Radiation shi...

Страница 27: ...al 300 silicone sealant around edge of fireplace and drywall Figure 7 1 Non combustible Facing A Finishing Material Refer to Sections 1 B and Sections 1 C for combustible non combustible materials Ref...

Страница 28: ...t a k value to an R value Refer to Table 7 2 for hearth extension insulation alternatives WARNING Risk of Fire Hearth extensions are to be installed only as illustrated to prevent high temperatures fr...

Страница 29: ...e Metal Hearth Strip is required under the front of the fireplace Tile stone or other non combustible material Floor constructed of wood or other combustible material Fireplace Opening 4 in 102 mm min...

Страница 30: ...e hearth framing must be constructed of non combustible materials such as metal framing or equivalent material and placed on HX3 s HX4 s or equivalent material When creating the platform allow for the...

Страница 31: ...andoffs Measured from top of fireplace opening 12 in 305 mm 1 1 2 in 38 mm maximum 12 in 305 mm minimum 6 in 152 mm minimum Combustible Decorative Facing Seal joint with non combustible sealant Non co...

Страница 32: ...n 305 mm 11 1 4 in 286 mm FLUSH FRONT 4 in 102 mm BRICK FRONT 5 0 a n g l e 39 angle Grid represents 1 scale Figure 7 11 Mantel Leg Surround or Wall Projection acceptable on both sides of opening E Si...

Страница 33: ...as Log Lighter Provision WARNING Fire and or Asphyxiation Risk Use with solid wood fuel or decorative gas appliance only Gas fire generates fumes DO NOT install unvented gas logs Damper must be locked...

Страница 34: ...ney Offset Return 30 deg FS338 Ceiling Firestop Straight FS339 Ceiling Firestop 15 deg FS340 Ceiling Firestop 30 deg AS8 SL300 Straight Attic Insulation Shield 24 in 610 mm JB877 Chimney Joint Band CB...

Страница 35: ...F370 Roof Flashing JB877 Chimney Joint Band 2 in 51 mm 10 1 2 in 267 mm 24 5 8 in 625 mm 27 3 8 in 695 mm 12 in 305 mm 31 in 787 mm 24 5 8 in 625 mm 12 in 305 mm TR TVK Top Vent Kit Catalog A B FS338...

Страница 36: ...nstallation Manual Rev J 09 18 TR344 Round Termination Cap 15 3 4 in 400 mm TR342 Round Telescoping Termination Cap TR342 B Round Telescoping Termination Cap ST375 Square Termination Cap TS345 TS345P...

Страница 37: ...Installation Manual Rev J 09 18 B A C B C A DTS134 DTS146 DTO134 DTO146 Decorative Caps DTO134 A B C in 34 20 24 mm 864 508 610 DTO146 in 46 22 7 26 mm 1168 576 660 DTS134 A B C in 34 21 18 24 mm 864...

Страница 38: ...n 13 mm HX3 Hearth Extension B Optional Components LDSCP M Corner Post Kit for custom size Bifold Glass Doors DM1036 DM1042 2 Wire Ties Fastener Pack Outside Air Hood Outside Air Plate Assembly AK24 O...

Страница 39: ...39 Majestic Royalton Series BE36 42 4044 197 Installation Manual Rev J 09 18 Majestic a brand of Hearth Home Technologies 7571 215th Street West Lakeville MN 55044 www majesticproducts com...

Отзывы: