16
Majestic • MERC32IN, MERC32IL, MERC32VN, MERC32VL Installation Manual • 2401-980 Rev. C • 11/16
G. Vent Diagrams
V
1
Minimum
*
H
1
Maximum
**
90 Elbow Only
2 ft.
610 mm
1/2 ft.
152 mm
2 ft.
610 mm
1-1/2 ft.
457 mm
3 ft.
914 mm
2-1/2 ft.
762 mm
5 ft.
1.5 m
3-1/2 ft.
1.1 m
7 ft.
2.1 m
4-1/2 ft.
1.4 m
15 ft.
4.6 m
H
1
MAX. =15 ft. (4.6 m)
V
1
+ H
1
MAX. = 40 ft. (12.2 m)
*
See Warning.
Figure 4.7
1. Top Vent - Horizontal Termination
One Elbow
Fire Risk.
• When using SLP-HRC-SS termination cap on top
vented
fi
replaces, a one foot minimum vertical
vent section is required before installing first
elbow.
• Elbow heat shield required when V1 is less than
1-1/2 ft. Clearances to combustibles MUST be
maintained. See Section 5.A.
WARNING*
Note: Use SLP Series
components only.
**
Note
: When using
SLP-FLEX (6-5/8 in.)
venting, there
MUST be a 25% reduction in total H when using
fl
ex vent.
When using
SLP-FLEX7 (7 in.)
venting, refer to the venting
tables included with the adapter collar kit.
H
1
V
1