21
Majestic • MARQ42STIN Installation Manual • 2272-980 Rev. H • 4/21
Figure 4.12
Figure 4.13
Top Vent - Vertical Termination
No Elbow
V
1
V
1
= 50 ft. Max. (15.2 m)
V
1
= 3 ft. Min. (914 mm)
H
1
V
1
V
2
V
1
H
1
V
2
2 ft
610 mm
1 ft
305 mm
*
3 ft
914 mm
3 ft
914 mm
*
4 ft
1.2 m
4 ft
1.2 m
*
5 ft
1.5 m
9 ft
2.7 m
*
6 ft
1.8 m
12 ft
3.7 m
*
V
1
+ V
2
+ H
1
= 50 ft (15.2 m) Max.
*No specific restrictions on this value EXCEPT
V
1
+ V
2
+ H
1
cannot exceed 60 ft (18.3 m).
After V
1
= 6 ft, then H
1
Max.= V
1
x 2
FLUE RESTRICTOR
NOTE:
Flue Restrictor ships in
manual bag assembly.
Note:
Flue restrictor is permit
-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
Note:
Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.
Note:
Flue restrictor is permit
-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.
Note:
Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.